VFD500 high performance vector control frequency inverter user manual Appendix A Modbus communication protocol
3)Inverter fault description: read the inverter fault see 25.00 function code (0x1900)
VFD Fault
address
0000:no fault
0001:SC protection
0002:overcurrent during acceleration
0003:overcurrent during deceleration
0004:overcurrent at constant speed
0005:overvoltage during acceleration
0006:overvoltage during deceleration
0007:overvoltage at constant speed
0008:low voltage fault
0x1900
0009:contactor open
(25.00 function
000A:VFD overload
code)
000B:motor overload
000C:power input phase loss
000D:power output phase loss
000E:IGBT module overheat
000F:Reserved
0010:motor over heat
0011:fast overcurrent time out fault
0012:Ground fault
0013:motor auto tuning fault reserved
0014: drives temperature detection fault
A.7 Register data type
There are several types of register data, and each type of communication setting method is shown
in the following table:
Types of register data
16-bit unsigned
number
16-bit signed number
Binary number
"One hundred
thousand" type
VFD trip information
Communication setting method
0~65535 corresponds to 0xFFFF; the decimal point does
not need to be processed. Example, Set P00.07 to 40.00Hz:
Write 0x0FA0 to the 0x0007 address.
-32768~32767 corresponds to 0x8000~0x7FFFF.
Example: Set P14.01 to -50.0%:
Write 0xFE0C to the 0x0E01 address.
Represents a value of 16 bits.
For example, the content of the 0x0600 address is 0x0012,
which means:Bit1 of r06.00=1, bit4=1; that is, DI1 and DI5
(HDI) are valid.。
"Units" ~ "Thousands" correspond to 0~3bit, 4~7bit, 8~11bit,
12~15bit respectively.
Example: Set the "Unit'digit" of P40.04 to AI1 and "ten's
digit" to AI2:
Write 0x0021 to the 0x2804 address.
- 146-
0015:current detection fault
0016:PG card feedback fault
0017:Encoder zero detection fault
0018:Reserved
0019:overspeed
001A:too large speed deviation
001B: motor auto tuning fault 1
001C: motor auto tuning fault 2
001D: motor auto tuning fault 3
001E:motor auto tuning fault 4
001F:off load
0020:Eeprom read and write fault
0021:Reserved
0022:Communication time out fault
0023:extension card fault
0024:PID feedback lost during running
0025:User-defined fault 1
0026:User-defined fault 2

Hide quick links: