Veikong VFD500 Series User Manual page 132

High performance vector and torque control frequency inverter
Hide thumbs Also See for VFD500 Series:
Table of Contents

Advertisement

VFD500 high performance vector control frequency inverter user manual
Fault
Fault Name
code
PID
feedback
36
lost during
running
User-
defined
37
fault 1
User-
defined
38
fault 2
The fault code is used for the communication read fault type: when the communication reads
the registers r25.00, r26.00, r26.08, r26.16, the register contents of the reply are fault coded.
6.2 Warning type
The warning is used to remind and inform the user of the current state of the inverter. When the warning
occurs, the keypad will display a warning message, and the warning will automatically reset when the
warning is cleared. Some warnings require the user to check the cause before running the drive, and
some do not care. Warning As an instant reminder, the drive does not store the corresponding information.
Bit 12 of r27.10 indicates whether there is a warning message currently.
Warning
Warning
name
code
Insufficient
1
power
Wrong
2
parameter
Sleeping
5
status
The warning code is used for the communication read warning type: when the communication
reads register r25.16, the contents of the returned register are the warning code.
Possible Causes
Display
1、 PID feedback<P40.35 setting
Er.FbL
value and P40.36 not zero,PID
feedback>P40.37 setting
value and P40.38 not zero
1: The signal of user-defined fault
1 is
Er.Ud1
input via DI.
2:The signal of user-defined fault 1
is
input via virtual I/O.
1: The signal of user-defined fault
2 is
Er.Ud2
input via DI.
2:The signal of user-defined fault 2
is
input via virtual I/O.
Display
PoFF
1: The DC link voltage is insufficient
and cannot be started normally.
1: The parameter settings are wrong,
such as:
A.PARA
The torque mode is set in the VF
control mode.
1. The system is in a sleep state, and
SLEEP
the system will automatically start
when hibernation is over.
Chapter6 Fault diagnosis and solutions
1、 Check PID feedback signal
2、 P40.35 and P40.37 set
1: Reset the operation.
2: Reset the operation
1: Reset the operation.
2: Reset the operation
Reason
- 130-
Solutions
correct parameter
Measure
1:Check if the inverter power
supply is normal.
1:Modify and check the
parameter compatibility
problem
1:Generally no need to pay
attention to it