Chapter 5 Function code
When PID reference source is digital setting, PID digital setting 0~3 depends on DI terminal function 43 (preset PID
terminal I ) and 44 ( preset PID terminal 2):
preset PID terminal1
ineffective
ineffective
effective
effective
For example: When AI1 is used as PID feedback, if the full range corresponds to 16.0kg pressure and require PID
control to be 8.0kg; then set P40.05 PID feedback range to 16.00, PID digital reference terminal select to P40.06,
Set P40.06 (PID preset setting 0) to be 8.00
Function
Parameter name
code
PID reference
P40.10
source selection
PID feedback
P40.11
source1
PID Feedback
P40.12
range
PID feedback
P40.13
function selection
VFD500 high performance vector control frequency inverter user manual
preset PID terminal 2
ineffective
effective
ineffective
effective
Description
0:ref1
1:ref1+ref2
2:ref1-ref2
3:ref1*ref2
4:ref1/ref2
5:Min(ref1,ref2)
6:Max(ref1,ref2)
7(ref1+ref2)/2
8: fdb1and fdb2 switchover
Unit's digit 0:PID feedback source1(fdb1)
0:AI1
1:AI2
2:AI3(option card)
3:AI4(option card)
4: PLUSE(HDI)
5: Communication
6: Motor rated output current
7: Motor rated output frequency
8: Motor rated output torque
9: Motor rated output frequency
Ten's digit : PID feedback source2 (fdb2)
Same as Unit's digit
0.01~655.35
0:fdb1
1:fdb1+fdb2
2:fdb1-fdb2
3:fdb1*fdb2
4:fdb1/fdb2
5:Min(fdb1,fdb2)Take fdb1.fdb2 smaller value
6:Max(fdb1,fdb2) Take fdb1.fdb2 bigger value
7: (ref1+ref2)/2
8: fdb1and fdb2 switchover
- 106-
PID Digital setting value(0.1%)
P40.06 * 100.0% / P40.05
P40.07 * 100.0% / P40.05
P40.08 * 100.0% / P40.05
P40.09 * 100.0% / P40.05
Default
0
00
100.00
0
Property
☆
☆
☆
☆