Chapter 5 Function code
Function
Parameter name
code
Droop control filtering
P01.42
time
When several motors drive the same load, each motor's load is different because of the difference of
motor's rated speed. The load of different motors can be balanced through droop control function which
makes the speed droop along with load increase.
When the motor outputs rated torque, actual frequency drop is equal to P1.41. User can adjust this
parameter from small to big gradually during commissioning.
P01.43
Textile frequency setting
P01.44
Textile frequency
P01.45
Jump frequency
P01.46
Textile period
Triangle wave rising
P01.47
time coefficient
This function is mostly used in textile and chemical industry and some application such as traversing and winding so
it is used for balancing the workload allocation when multiple motors are used to drive the same load. The output
frequency of the frequency inverters decreases as the load increases. You can reduce the workload of the motor
under load by decreasing the output frequency for this motor, implementing workload balancing among multiple
motors.P01.44 or P01.46=0,This function disable
Output frequency
Frequency
swing limit
Frequency
swing center
Frequency swing
lower limit
Start acceleration
Running
command
VFD500 high performance vector control frequency inverter user manual
Description
Frequency drop volume: Max
frequency*P01.41*Current load/rated load
0.000s~10.000s
0: relative to center of textile frequency
1: relative to maximum frequency
0.0%~100% relative to center of textile
frequency P01.43 = 0Textile frequency Aw =
P01.44 * center frequency
P01.43 = 1: Textile frequency Aw = P01.44 *
max frequency
0.0%~50.0% relative to textile frequency
0.1s~3000.0s
0.1%~100.0% relative to textile period
Frequency swing range:AW-set the frequency(choose
P01.43)*P01.44 Kick-hop frequency:jw-aw*P01.45
Jw
Jw
Triangle wave rise time:
P01.47*frequency swing
cycle
Frequency swing
cycle (P01.46)
- 46-
Default
Property
0.050s
0
0.0%
0.0%
10.0s
50.0%
+A
w
-Aw
Deceleration stop