Veikong VFD500-PV Series Operation Manual

Veikong VFD500-PV Series Operation Manual

Solar pumping inverter
Hide thumbs Also See for VFD500-PV Series:

Advertisement

Operation manual
VFD500-PV Series
Solar pumping Inverter

Advertisement

Table of Contents
loading

Summary of Contents for Veikong VFD500-PV Series

  • Page 1 Operation manual VFD500-PV Series Solar pumping Inverter...
  • Page 2 Solar pumping inverter fast user guide 1、Electrical cable Connection Please follow the diagram below for wiring. And pay attention to the following issues: DC-LINK POWER MOTOR 2.2KW-15KW 18.5KW-22KW 30KW-37KW 45KW-90KW...
  • Page 3 Terminal Function instruction R、S、T AC power input terminal, connect three-phase AC power U、V、W AC output terminal, connect three-phase AC motor The positive and negative terminals of the internal DC bus are connected 、 to solar panel 、PB Braking resistor connection terminal when built-in brake unit Ground terminal, ground Safety capacitor and varistor grounding selection screw (SIZEA~SIZEC EMC EMC、VDR...
  • Page 4 Solar panels 3 phase power input Main circuit Control circuit 485+ RS485 port Connector slip 485- +24V +24V Start/stop terminal AO1、AO2 output: ~ ~ 10V/0 20mA +10V Water tank level Relay 1 output, feedback Default is fault signal output OFF OFF ON ON Grounding Solar pump inverter diagram 1-1...
  • Page 5 3、Trial run(How to use and start solar pump inverter) Step 1: Keyboard control: Set motor parameter P11.02- P11.05 as per motor pump name plate. If dry run protection is required, measure the unload protection current according to the following method. If dry run protection is not required then move to step 2 Notice: Unload detection current self-learning: disable the PV pump function (P47.00=0), run to 30~40Hz, when the output frequency is stable, enter P24.13, press the keyboard...
  • Page 6 Fault code (r25.00)  DC bus voltage at fault (r25.03)  Output frequency at fault (r25.01)  Output current at fault (r25.02)  Output power at fault (r25. 16)  fault code 4.2 Menu mode After the inverter is power on, the keyboard menu mode is user-defined mode. Most of users only need to pay attention to the parameters displayed in this mode.
  • Page 7 Function Name Description Default Property code 0: MPPT is disabled; CVT control is used (voltage is given as P47.04). 1: Enable MPPT. The remaining time of the starting is Remaining time for ● r47.02 displayed In auto start mode, starting Unit: second In auto start mode, set the time from power ★...
  • Page 8 Function Name Description Default Property code continue to accumulate on the original basis after re-powering. It Can be cleared to zero by P47.14. Set 1 to clear zero for r47.12. This function Cumulative pumping ☆ P47.14 code automatically changes to 0 after the reset reset is completed.
  • Page 9 Function Name Description Default Property code ☆ P41.06 Wake-up delay 0.0s~6000.0s 0.0s Basic function parameter 0 ~ 65535  No user password status (P00.01 = 1 after power-on): Entering the same non-zero value twice in succession sets a user password and enters lockout.
  • Page 10 Function Name Description Default Property code Notice:DI terminal function code 26-32 superior than this function code ★ P01.06 Maximum frequency 10.00~600.00Hz 50.00Hz 0:ramp to stop ☆ P02.08 Stop method 1:free coast to stop Setting value depend on P03.16 P03.16 = 2, 0.00~600.00s; Depend on ☆...
  • Page 11 Function Name Description Default Property code faults Ten’unit:Undervoltage stall control 0:undervoltage stall disabled 1:undervoltage stall deceleration(decelerate to zero speed and run at zero speed) 2: undervoltage stall deceleration(decelerate to zero and stop)  The undervoltage stall function reduces the motor power consumption or reduces the power consumption of the motor or turns it into a power generation operation to avoid the undervoltage fault on the DC side.
  • Page 12 Chapter 6 Fault Diagnosis and Solution VFD500-PV solar pump inverter has 24 types of warning information and protection function. In case of abnormal fault,the protection function will be invoked, the inverter will stop output, and the faulty relay contact of the inverter will start, and the fault code will be displayed on the display panel of the inverter. Before consulting the service department, the user can perform self-check according to the prompts of this chapter, analyze the fault cause and find out solution.
  • Page 13 Fault Name Solutions Display Possible Causes 1: The output circuit is grounded or 1: Eliminate external faults. short circuited. 2: Perform the motor 2: Motor auto-tuning is not performed. auto-tuning. Over current 3: The deceleration time is too short. 3: Increase the deceleration time. during Er.OC2 4: The voltage is too low.
  • Page 14 Fault Name Solutions Display Possible Causes 1: Instantaneous power failure occurs on the input power supply. 1: Reset the fault. 2: The frequency inverter's input 2:Adjust The voltage to normal voltage is not within the allowable range. range. Low voltage Er.LU1 3: Ask for technical support 3: The DC bus voltage is abnormal.
  • Page 15 Fault Name Solutions Display Possible Causes 1: The cable connecting the frequency 1:Eliminate external faults. inverter and the motor is faulty. 2: Check whether the 2: The frequency inverter's Power output Motor three phase winding Er.oLP three-phase outputs are unbalanced phase loss is normal.
  • Page 16 Fault Name Solutions Display Possible Causes EEPROM 1、 Eeprom Operate too frequent 1、 Operate Eeprom suitable read- write Er.EEP 2、 Replace the main control board 2、 The EEPROM chip is damaged. fault 1、Confirm whether the load is off 1、The frequency inverter running 2、Check that the load is Dry run/unload Er.
  • Page 17 ShenZhen VEIKONG Electric CO., Ltd. Factory Address: Block E01,first industrical park lingbei 5 road ,phoenix community,f uyong street , Bao'anDistrict, Shenzhen ,China R&D Center: Jin yu cheng building A,Bu Long Rd Bantian Town ,Longgang district Shenzhen City,China Technical Support Hotline: +86-0755-89587650...