Veikong VFD500 Series User Manual page 43

High performance vector and torque control frequency inverter
Hide thumbs Also See for VFD500 Series:
Table of Contents

Advertisement

Chapter 5 Function code
Function
Parameter name
code
Main frequency
P01.00
source selection (A)
Auxiliary frequency
P01.01
source selection (B)
Reference option for
P01.02
auxiliary frequency
source
Auxiliary frequency
P01.03
gains
Frequency source
P01.04
selection
Main and Auxiliary
P01.05
arithmetic
P01.06
Maximum frequency
Upper limit frequency
P01.07
control
VFD500 high performance vector control frequency inverter user manual
01Group frequency source selection
Description
0:Digital setting
1:AI1
2:AI2
3:AI3(IO extension card)
4:AI4(IO extension card)
5:HDI
6:multi-step speed
7:communication
8:PID
9:Internal PLC
Notice: DI terminal function code 26-32
superior than this function code
Same as P01.00
Notice: DI terminal function code 33 superior
than this function code
0:Relative to Maximum frequency
1:Relative to main frequency
0.0~300.0
0:main frequency source A
1:auxiliary frequency source B
2:Main and auxiliary arithmetic results
3:Switchover between main and auxiliary
frequency
4:switchover between main frequency source
A and A+B Arithmetic results
5:Switchover between B and (A+B)
(*)DI function code 25 effective to
corresponding terminal ,frequency will adopt
the latter
0:A+B
1:A-B
2:The bigger of main A and Auxiliary B
3:The smaller of Main A and Auxiliary B
4:A*B
A*B have better frequency adjustment ,widely
used for winding industry, fine sand machine,
and leather, paper industry...
10.00~600.00Hz
0:digital setting (set through P01.08)
1:AI1
2:AI2
- 41-
Default
Property
0
0
0
100.0%
0
0
50.00Hz
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents