Digital Input; 1-Button Operation/Construction Site Mode - WAGO 753-1630 Manual

Smi master module 230 v ac
Table of Contents

Advertisement

28
Function Description
4.1.1

Digital Input

The digital input can be parameterized to use one of the following functions:
The digital input can be parameterized to use one of the following functions:

• 1-button operation/construction site mode

• Trigger for safety position
• No function in the SMI module; evaluation of the digital input in the PLC
The digital input corresponds to IEC 61131-2, Type 1.
An open input is recognized as a low signal.
1-button operation/construction site mode is activated by default (factory setting).
Note
Do not modify function of digital input while safety position active
If the safety position is triggered via the digital input and the function of the
digital input is then changed to "no function" or "construction site mode,"
then the drive remains in safety position even once the cause for entering
safety position has been eliminated, since the digital input does not process
the corresponding signal.
Pos: 71.3 /Serie 753 (WAGO-I/O-SYSTEM)/Funktionsbeschreibung/Funktionsbeschreibung 753-1630, -1631/Funktionsbeschreibung 753-1630, -1631 - Feldbuskopplermodus - 1-Taster-Betrieb/Baustellenmodus @ 28\mod_1478704015695_21.docx @ 386589 @ 3 @ 1
4.1.2
1-Button Operation/Construction Site Mode
1-button operation (also called construction site mode) enables control of SMI
drives, e.g., for test purposes before system integration or for processing alarm
messages.
For this purpose, an external button is connected to the digital input and
connected to the power supply.
The break contact logic or make contact logic can be parameterized for the
trigger event.
Motion commands are triggered by pressing the button and sent to all connected
SMI drives.
The following motion commands are possible:
• Move up
• Move down
• Stop
The motion commands can also be executed as an up command and down
command. If a motion command is being executed, pressing the button stops the
SMI drive. If you press the button again, the SMI drives reverses direction.
Pos: 71.4 /Serie 753 (WAGO-I/O-SYSTEM)/Funktionsbeschreibung/Funktionsbeschreibung 753-1630, -1631/Funktionsbeschreibung 753-1630, -1631 - FBK-Modus - Zwangsposition @ 28\mod_1478704016177_21.docx @ 386635 @ 3 @ 1
Manual
Version 1.2.0 FW/HW Version 02/01
753-1630 SMI Master Module 230 V AC

Advertisement

Table of Contents
loading

This manual is also suitable for:

I/o system 750 seriesI/o system 750/753753-1631

Table of Contents