Table 7-1
Reported
SAC
02
Type 2 library software errors including microcode and operating system
errors.
Action 1
To recover from the error, shutdown and restart the library by using the
Operator Panel (Main Menu Mode Dialog) or the Main Circuit Breaker
switch on the AC Power Compartment in the lower right corner at the back of
the CM. For more information, refer to Shutting Down the Scalar 1000 on page
4-9 and Starting the Scalar 1000 on page 4-7.
Note: Wait at least one minute between powering off and powering on the
library.
Action 2
If the problem is not corrected or persists, retrieve command and error log
information. Refer to Viewing Diagnostic Files (Library and RMU Logs) on page
4-20 for information on how to retrieve logs.
Action 3
Contact ATAC. Refer to ADIC Technical Assistance Center on page 1-5 for ATAC
contact information.
03
Type 3 library software errors including microcode and operating system
errors.
Action 1
To recover from the error, shutdown and restart the library by using the
Operator Panel (Main Menu Mode Dialog) or the Main Circuit Breaker
switch on the AC Power Compartment in the lower right corner at the back of
the CM. For more information, refer to Shutting Down the Scalar 1000 on page
4-9 and Starting the Scalar 1000 on page 4-7.
Note: Wait at least one minute between powering off and powering on the
library.
Action 2
If the problem is not corrected or persists, retrieve command and error log
information. Refer to Viewing Diagnostic Files (Library and RMU Logs) on page
4-20 for information on how to retrieve logs.
Action 3
Contact ATAC. Refer to ADIC Technical Assistance Center on page 1-5 for ATAC
contact information.
22 June 2004
SAC Reporting (Continued)
Perform these actions
Service Action Codes
7-5