3.4.6 Wire sizes and protection device ratings
Table 2 describes the wire sizes to be used for AC input power and motor output connections,
together with the ratings for protection devices.
Catalog Number
FDH1A02xx-xxxx
FPH1A02xx-xxxx
FDH2A02xx-xxxx
FPH2A02xx-xxxx
FDH1A05xx-xxxx
FPH1A05xx-xxxx
FDH2A05xx-xxxx
FPH2A05xx-xxxx
FDH1A07xx-xxxx
FPH1A07xx-xxxx
FDH2A07xx-xxxx
FPH2A07xx-xxxx
FDH4A02xx-xxxx
FPH4A02xx-xxxx
FDH4A05xx-xxxx
FPH4A05xx-xxxx
FDH4A07xx-xxxx
FPH4A07xx-xxxx
FDH2A15xx-xxxx
FPH2A15xx-xxxx
FDH4A15xx-xxxx
FPH4A15xx-xxxx
FDH4A20xx-xxxx
FPH4A20xx-xxxx
FDH4A27xx-xxxx
FPH4A27xx-xxxx
Note: All wire sizes are based on 75°C (167°F) copper wire. Higher temperature smaller
MN1902
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Nominal
Input
Input
Voltage
Voltage
115V (1Φ)
230V (1Φ)
115V (1Φ)
230V (1Φ)
115V (1Φ)
230V (1Φ)
230-460V
(3Φ)
230-460V
(3Φ)
230-460V
(3Φ)
230V (3Φ)
230-460V
(3Φ)
230-460V
(3Φ)
230-460V
(3Φ)
Table 2 - Protection device and wire ratings
gauge wire may be used per National Electric Code (NEC) and local codes.
Recommended fuses/breakers are based on 25°C (77°F) ambient, maximum
continuous control output current and no harmonic current. Earth/ground wires
must be the same gauge, or larger, than the Line and Neutral wires.
Incoming Power
Continuous
D-Type
yp
Output
Output
Input
Input
Amps
Amps
Breaker
Breaker
(RMS)
(A)
2.5A
6
2.5A
6
5A
10
5A
10
7.5A
16
7.5A
16
2.5A
6
5A
10
7.5A
16
15A
32
15A
32
20A
40
27.5A
60
www.baldormotion.com
Time
Minimum
Minimum
Delay
Delay
Wire Gauge
Input
Input
Fuse
AWG
(A)
6
14
6
14
10
14
10
14
16
14
16
14
6
14
10
14
16
14
32
12
32
12
40
10
60
10
Basic Installation 3-13
2
mm
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
3.3
3.3
5.3
5.3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Flex+drive ii

Table of Contents