Baldor FDH1A05TB-EN20 Installation Manual page 154

Table of Contents

Advertisement

D.1.3 Use of CE compliant components
The following points should be considered:
Using CE approved components will not guarantee a CE compliant system!
H
The components used in the drive, installation methods used, materials selected for
H
interconnection of components are important.
The installation methods, interconnection materials, shielding, filtering and
H
earthing/grounding of the system as a whole will determine CE compliance.
The responsibility of CE mark compliance rests entirely with the party who offers the end
H
system for sale (such as an OEM or system integrator).
D.1.4 EMC wiring technique
Cabinet
Using a typical electroplated zinc coated enclosure, connected to earth/ground, means that all
parts mounted on the back plane are connected to earth/ground and all outer shield (screen)
connections can be connected to earth/ground. Within the cabinet there should be a spatial
separation between power wiring (motor and AC power cables) and control wiring.
Shield (screen) connections
All connections between components must use shielded cables. The cable shields must be
connected to the enclosure. Use conductive clamps to ensure good earth/ground connection.
With this technique, a good earth/ground shield can be achieved.
EMC filters
The filter should be mounted next to the FlexDrive
and the filter should use shielded (screened) cables. The cable shields should be connected to
shield clamps at both ends. An exception to this is the analog demand signal.
Earthing/grounding
For safety reasons (VDE0160), all Baldor components must be connected to earth/ground with
a separate wire. Earth/ground connections must be made from the central earth/ground (star
point) to the regeneration resistor enclosure and from the central earth/ground (star point) to
the power supply.
MN1902
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
II
. The connections between the FlexDrive
www.baldormotion.com
II
CE & UL D-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Flex+drive ii