5.4.3.5

IP address and the subnet mask in the project

Overview
After you have assigned an IP address to the drive, check the IP address and subnet mask set in
the project. An online connection can only be established when the settings in the project and
in the drive are identical.
Procedure
To compare the IP address and subnet mask in the project and drive, proceed as follows:
1. Search for the drive under "Online access" and "Update accessible devices".
The drive is displayed with IP address and subnet mask.
2. Switch to the device view.
3. Select the PROFINET interface.
4. In the inspector window, select "Properties" > "General".
5. Click "Ethernet addresses".
The properties of the interface are displayed.
6. Compare the IP address and subnet mask with the settings under "Online access".
Result
If both settings are the same, you can establish an online connection.
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
5.4 Establishing an online connection to the drive
Commissioning
163