Commissioning
5.3 Creating a project offline
Note
Switching on a new/modified network
When first switched on with a new/modified network, an automatic controller setting must be
implemented using the line and DC link identification routine (p3410). While the identification
routine is running, it is not permissible for other loads to be switched in/switched out.
Procedure
To make detailed settings for an infeed unit, proceed as follows:
1. Select the infeed in the device view and open the inspector window.
2. Select the "Line Module details > Line Module settings" menu in the inspector window.
In the screen form, the following setting options are displayed:
120
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2