6.1.4.4

Terminal Module TM120

Table 6-37
Meaning of the LEDs on the Terminal Module TM120
LED
Color
Status
READY
-
Off
Green
Continuous
light
Orange
Continuous
light
Red
Continuous
light
Green/
Flashing
red
light
0.5 Hz
Flashing
light
2 Hz
Green/
Flashing
orange
light
or
2 Hz
red/
orange
1)
The parameter for activating component recognition using LEDs can be taken from the following reference:
Reference: SINAMICS S120/S150 List Manual
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
Description, cause
The electronics power supply is missing or outside the permis‐
sible tolerance range.
The component is ready for operation. Cyclic DRIVE-CLiQ com‐
munication is taking place.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is activated irrespective of whether the corresponding
messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. The system waits for POWER
ON.
Component recognition via LED is activated
Note:
Both options depend on the LED status when component rec‐
ognition is activated.
6.1 Diagnostics using LEDs
Remedy
Check the power sup‐
ply.
-
-
Remove and acknowl‐
edge the fault.
-
Carry out a POWER
ON.
.
-
1)
Diagnostics
309