Control Unit 320-2 PN during operation
Table 6-7
CU320-2 PN Control Unit – description of the LEDs after powering up
LED
Color
RDY
Green
Red
Red/
green
Orange
Green/
orange
or
red/
orange
Green/
orange
or
red/
orange
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
Display
Description, cause, remedy
OFF
Electronics power supply is missing or outside permissible toler‐
ance range.
Remedy: Check the power supply.
Continuous light
The component is ready for operation and cyclic DRIVE-CLiQ com‐
munication is taking place.
Flashing light
Commissioning/reset
0.5 Hz
Flashing light
Writing to the memory card
2 Hz
Flashing light with the
Indicates PROFIenergy energy-saving mode.
on/off ratio
0.5 s = On
3 s = Off
Flashing light
General errors
2 Hz
Remedy: Check parameterization / configuration data
Flashing light
Control Unit is ready. However, software licenses are missing.
0.5 Hz
Remedy: Obtain licenses.
Flashing light
Updating the firmware of the DRIVE-CLiQ components
0.5 Hz
Flashing light
DRIVE-CLiQ component firmware update complete. Wait for POW‐
2 Hz
ER ON for the components in question.
Remedy: Carry out a POWER ON for the components in question
Flashing light
Control Unit detection via DCP flashing
1 Hz
Remark:
Both options depend on the LED status when component recog‐
nition is activated via DCP.
Flashing light
LED-supported detection of Control Unit is activated
2 Hz
(p0124[0] = 1).
Remark:
Both options depend on the LED status when component recog‐
nition is activated via p0124[0] → 1.
Diagnostics
6.1 Diagnostics using LEDs
.
1)