Test Data; Reference Conditions According To Iec 62586-1 For Determining Test Data; Electrical Tests - Siemens SICAM Q100 7KG95 Series Manual

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

14.2

Test Data

Reference Conditions according to IEC 62586-1 for Determining Test Data

14.2.1
Ambient temperature
Relative humidity
Supply voltage
Phases (3-wire network)
External continuous magnetic fields
DC components V/I
Signal waveform
Frequency
Voltage magnitude
Flicker
Unbalance (all channels)
Harmonic
Interharmonic

Electrical Tests

14.2.2
Standards
Standards
Insulation Test according to IEC EN 61010-1 and IEC EN 61010-2-030
Inputs/Outputs
Current measurement
inputs
Voltage measurement
inputs
Supply voltage
Binary outputs
Binary inputs
Ethernet interface
RS485 interface
EMC Tests for Immunity (Type Tests)
Standards
Electrostatic discharge,
Class III, IEC 61000-4-2
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Insulation
Rated Voltage
Reinforced
150 V
Reinforced
600 V
300 V
Reinforced
300 V
Reinforced
300 V
Reinforced
300 V
SELV
< 24 V
SELV
< 24 V
23 °C ± 2 °C
40 % to 60 % RH
V
± 1 %
PS
3
DC field: ≤ 40 A/m
AC field: ≤ 3 A/m
None
Sinus
50 Hz ± 0.5 Hz
60 Hz ± 0.5 Hz
Udin ± 1 %
Pst < 0.1 %
100 % ± 0.5 % of Udin
0 % to 3 % of Udin
0 % to 0.5 % of Udin
IEC EN 61000-6-2
IEC EN 61000-6-4
IEC EN 61010-1
IEC EN 61010-2-030
ISO Test Voltage
AC 2.3 kV
Surge voltage
9.76 kV
DC 3.125 kV
AC 3.536 kV
AC 3.536 kV
AC 1500 V
DC 700 V
IEC EN 61000-6-2
For more standards see also individual functions
6 kV contact discharge
8 kV air discharge, both polarities
150 pF, Ri = 330 Ω with connected Ethernet cable
Technical Data
14.2 Test Data
Category
Cat. III
Cat. III
Cat. IV
Cat. III
Cat. III
Cat. III
335

Advertisement

Table of Contents
loading

Table of Contents