Troubleshooting, Repair, and Fallback Mode
12.2 Fallback Mode
NOTE
i
i
The whole operation takes more than 3 min, and must not be interrupted, for example by a power loss;
otherwise, the device cannot recover and must be sent back to the factory.
NOTE
i
i
If you forget the user credentials, it is the only way to set the device in the factory state to create a new
admin or User Account Manager.
To access to other functions, log on with the right user name and password.
If you have no user account, create the initial user account firstly.
[sc_initial account in fallback, 1, en_US]
Figure 12-4
After you log on successfully, the Maintenance tab will be added with the following sections depending on
the user roles:
Firmware upload
Run calibration
Save customer care support file
Parameter reset
Error log
324
Fallback Mode, Create the Initial User Account
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021