Measuring and Recording
3.2 Measurement and Evaluation Functions
[sc_harmonic power, instantaneous, 2, en_US]
Figure 3-10
The harmonics power function supports to hide harmonics that you are not interested in from the display
table. You can set the value from which amount of the harmonics power is hidden on the display via the
parameter Hide Harmonic when apparent power is lower than x.xxx VA displayed above the measurement
table. If you press the ENTER key, the value set for this parameter is active. It is not necessary to activate the
parameter.
If one of the spectral lines ±5 Hz of the harmonic frequency is greater than 2 % of the RMS value of the
harmonic, the corresponding value is displayed in blue as an indication.
The sign of the active power of the single harmonic determines the power-flow direction:
Positive sign: from the supply system to the demand
Negative sign: from the demand to the supply system
Value View of the Harmonics Power Direction
To display the measured values in the Value view tab, proceed as follows:
In the navigation window, click Harmonics power direction.
The aggregated values are displayed in a diagram.
110
Value View Tab, Harmonic Power, Instantaneous Value
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021