Power Quality
7.7 Waveform Records
Table 7-14
Parameter
Voltage trigger limits
Trigger active
Tolerance unit
Upper threshold
Lower threshold
Hysteresis
Detection mode
Current trigger limits
Trigger active
Tolerance unit
Upper threshold
Lower threshold
Hysteresis
Configuration binary trigger
Trigger active
Trigger source
Trigger value
Waveform capture setting
Total recording duration
Pretrigger ratio
Record ph-ph voltage
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Click Activation.
39
The detection mode will always synchronize with the setting of Record ph-ph voltage.
192
Settings for Trigger Management
Default Setting
Voltage event
Percentage
110.00 % of the primary nominal
voltage
90.00 % of the primary nominal voltage 0.00 % to 99.99 % of the primary
2.00 % of the primary nominal voltage
ph-N
39
No
Percentage
120.00 % of nominal current
00.00 % of nominal current
2.00 % of the nominal current
No
Binary Input 1
OFF
2.0 s
10%
No
Setting Range
No
User-defined
Voltage event
Percentage
Numerical
100.0 % to 10 000.0 % of the primary
nominal voltage
0.0 V to 1 000 000.0 V
nominal voltage
0.0 V to 1 000 000.0 V
0.0 % to 50.0 % of the primary nominal
voltage
ph-N
ph-ph
No
Yes
Percentage
Numerical
100.0 % to 10 000.0 % of of nominal
current
0.0 A to 1 000 000 A
0.00 % to 99.99 % of of nominal
current
0.0 A to 1 000 000.0 A
0.0 % to 50.0 % of the nominal current
No
Yes
Indication 1 from Remote
Indication 2 from Remote
Binary Input 1
Binary Input 2
ON
OFF
0.2 s to 3.0 s, increments of 0.2 s
0 % to 30 %, increments of 5 %
No
Yes
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021