Display and Administration

8.8 TCP/UDP Ports Used

8.8
TCP/UDP Ports Used
Communica-
Server/
tion Protocol
Client
HTTPS
Server
NTP
Client
Modbus TCP
Server
Modbus TCP
Server
IEC 61850
Server
SNMPv3
Server
(Agent)
Syslog
Client
RADIUS
Client
NOTE
i
i
One port cannot be assigned to more than one function at the same time.
240
TCP/UDP Port
Activated
by Default
TCP
443
Yes
UDP
123
No
TCP
502
Yes
TCP
503 to 65 535 No
TCP
102
No
UDP
161
No
UDP
514
No
UDP
10 000 to 65
No
535
(1812 by
default)
Description
TLS connection to a Web browser for device
configuration and value view
Time synchronization
Communication with a station controller using
Modbus TCP and Modbus default TCP port
Port number is configurable in the given range.
Communication with a station controller using
Modbus TCP and a user-defined TCP port.
Communication with a station controller using
IEC 61850
Network management
Syslog protocol