Basic Functions
2.4 AC Measurement
Parameter
Transformer settings
Voltage transformer
Primary rated voltage
Secondary rated voltage
Primary rated current
Secondary rated current
Primary rated current IN
Secondary rated current IN
Current inverse setting
Current inverse Ia
Current inverse Ib
Current inverse Ic
Current inverse IN
NOTE
i
i
If you change one of the following parameters, the device restarts:
Rated frequency
Network type
Power quality values for ph-N or ph-ph
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Click Activation.
NOTE
i
i
For setting operational parameters, follow the procedure for the device configuration described in chapter
11.12.3 Configuration of the
NOTE
i
i
If you change the Network type during ongoing operation, check settings, measured values, and limiting
values for inconsistencies. Check also the ICD/IID file which is suitable for the network type. If there are any
invalid measured values and limiting values or a wrong ICD file, restart the device.
Once you enable the voltage transformer, the parameter Voltage transformer is invisible on the HTML page. If you want to disable
6
the voltage transformer, you can set the same value for Primary rated voltage and Secondary rated voltage.
If you upgrade your firmware to V02.60, and want to set this parameter to the value from 1.0 V to 99.9 V, you must get the default
7
configuration firstly.
8
This parameter is to define whether the current direction is the same as the physical connection.
44
Default Setting
Yes
6
230.0 V
230.0 V
5.0 A
5.0 A
5.0 A
5.0 A
No
8
No
8
No
8
No
8
Device.
Setting Range
No
Yes
7
1.0 V to 1 000 000.0 V
1.0 V to 600.0 V
1.0 A to 100 000.0 A
1.0 A to 10.0 A
1.0 A to 100 000.0 A
Not configurable
The value is the same as the Secondary rated
current.
No
Yes
No
Yes
No
Yes
No
Yes
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021