Clearing the Min/Max Values

To clear the min/max values in the Maintenance tab, proceed as follows:
In the navigation window, click Min/Max values.
[sc_Reset min-max values, 3, en_US]
Figure 3-3
Click Clear Min/Max values.
The min/max values are cleared. The Action was successful indication is displayed on the status bar.

Harmonics, Interharmonics, Direction Harmonics

3.2.2
3.2.2.1

Function Description

Harmonic Power and Harmonic Angles
Measurement of phase angles is helpful to analyze different phenomena. It can be used for the following
purposes:
Evaluation of harmonic flows throughout the system
Identification of harmonic sources and harmonic sinks
Calculation of active, reactive, and apparent powers of harmonics
Assessment of harmonic current measurements in different points in the system
Modeling of disturbing loads and evaluation of their disturbing effect
Identification of measures to reduce the circuit feedback of the load
The device provides these measurements to support evaluation options that support the customer in mini-
mizing the influence of harmonics in the network or load, for example, when selecting the devices to reduce
the circuit feedback, filters, and reactive compensation.
Harmonic Directions
The device measures harmonics of voltages, currents, and powers up to the 31st order according to the
IEC 61000-4-7 standard.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Submenu Various Measured Quantities
Maintenance Tab, Clear Min/Max Values
Measuring and Recording
3.2 Measurement and Evaluation Functions
103