Siemens SICAM Q100 7KG95 Series Manual page 124

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Process Connections
4.2 Binary Inputs
Parameter
Binary inputs
19
Routed as:
Software filtering time
(only settable if Routed as: is
set to Status information)
Source inverted
Add entry to operational log
(only settable if Routed as: is
set to Status information)
Binary input indication
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Click Activation.
Value View of the Binary Inputs
To display the values of the binary inputs in the Value view tab, proceed as follows:
In the navigation window, click Binary inputs and outputs.
[sc_q100_BI_evaluation, 2, en_US]
Figure 4-2
Depending on the parameterization, either the status information or the source is evaluated.
The parameter cannot be changed in this field. In the Configuration tab, Energy management menu, select Load profile source or
19
Tariff source. If you did not select a source, Status information is automatically selected.
20
31 bytes of UTF-8
124
Default Setting
Status information
1 (* 2 ms)
no
yes
For example for terminal
U3/2:
Binary Input 2
Value View Tab, Binary Status (Binary Inputs)
Setting Range
Status information
Load profile source
Tariff source
2 ms to 120 000 ms
(settable in 2-ms increments)
no
yes
no
yes
20
Max. 31 characters
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021