Energy Management
6.2 Load Profile
The additional information is stored with the other load-profile data and can be retrieved via the communica-
tion interfaces.

Configuration and Value View via the User Interface

6.2.2
Configuration of the Load Profile
To change the settings of the load profile in the Configuration tab, proceed as follows:
In the navigation window, click Load/Energy profile.
[sc_configure_energy-profile, 2, en_US]
Figure 6-5
Configure the respective parameters according to the following table.
Table 6-2
Parameter
Subperiod time
Number of subperiods
24
Number = 1: Fixed Block method: The lengths of the subperiod and of the measuring period are identical; Number = 2 to 5: Rolling
Block method; Length of the subperiod: The length of the subperiod is an integer part of a full hour; Length of measuring period: The
length of the measuring period cannot be configured directly. It is defined as the product of the length of the subperiod and the
number of subperiods: Length of measuring period = n x length of subperiod; n = number of subperiods
152
Configuration Tab, Load/Energy Profile
Settings for Load Profile
Default Setting
15 min
1
24
Setting Range
1 min to 6 min in 1-min steps,
10 min, 12 min, 15 min, 20 min, 30 min, 60 min
1 to 5
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021