13 Technical Data
13.2 Test Data
13.2
Test Data
Reference Conditions according to IEC 62586-1 for Determining the Test Data
Ambient temperature
Relative humidity
Supply voltage
Phases (3-wire network)
External continuous magnetic fields
DC components V/I
Signal waveform
Frequency
Voltage magnitude
Flicker
Unbalance (all channels)
Harmonic
Interharmonic
13.2.1
Electrical Tests
Standards
Standards:
Insulation Test according to IEC EN 61010-1 and IEC EN 61010-2-030
Inputs/Outputs
Current measurement inputs
Voltage measurement inputs
Supply voltage
Binary outputs
Ethernet interface
RS485 interface
272
23 °C ± 2 °C
40 % to 60 % RH
V
± 1 %
PS
3
DC field: 40 A/m
AC field: 3 A/m
none
sinus
50 Hz ± 0.5 Hz
60 Hz ± 0.5 Hz
Udin ± 1 %
Pst < 0.1 %
100 % ± 0.5 % of Udin
0 % to 3 % of Udin
0 % to 0.5 % of Udin
IEC EN 61000-6-2
IEC EN 61000-6-4
IEC EN 61010-1
IEC EN 61010-2-030
Insulation
Rated
Voltage
Reinforced
150 V
Reinforced
480 V
Reinforced
300 V
Reinforced
300 V
Function
< 50 V
Function
< 50 V
ISO Test Voltage
AC 2.3 kV
Cat. III
Surge voltage
Cat. III
9.76 kV
DC 3.125 kV
Cat. III
AC 3.536 kV
Cat. III
DC 700 V
Cat. III
DC 700 V
Cat. III
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Category