Operational Indications and Operating Parameters
15.3 Advanced Functions
15.3.5.4

Trend Records

Table 15-34
Parameter
Tolerance unit
Tolerance number
Maximum recording
interval
15.3.5.5

Mains Signaling Voltage

Table 15-35
Parameter
Mains Signaling Voltage Measurement
MSV active
No. of MSV frequencies
Frequency 1
Frequency 2
Mains Signaling Voltage Capture Setting
Detection threshold
Total recording duration 75 s
Pretrigger ratio
15.3.5.6

Transient Detection

Table 15-36
Parameter
Transient reference level
366
Settings for Trend Recorder
Default Setting
Percentage
Percentage: 3 % of the primary nominal
voltage
Numerical: 0.5 V
10 min
Settings for Mains Signaling Voltage
Default Setting
No
1 frequency
216.60 Hz
1060.00 Hz
1.00 % of Un
10 %
Settings for Transient Detection
Default Setting
110 %
Setting Range
Percentage
Numerical
1 % to 5 %, increments of 1 %
0.2 V to 500.0 V
10 min
30 min
1 h
2 h
4 h
6 h
12 h
24 h
Setting Range
No
Yes
1 frequency
2 frequencies
100.00 Hz to 3000.00 Hz
100.00 Hz to 3000.00 Hz
1.00 % to 15.00 % of Un
15 s to 120 s, step: 15 s
0 % to 30 %, step: 5 %
Setting Range
110 % to 240 % of the primary nominal voltage
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021