12 Technical Data

12.2 Test Data

12.1.5

General Data

Battery
Internal memory
Degree of protection
DIN rail housing
Panel flush mounting (front)
Terminals
12.2
Test Data
Reference Conditions according to IEC 62586-1 for Determining the Test Data
Ambient temperature
Relative humidity
Supply voltage
Phases (3-wire network)
External continuous magnetic fields
DC components V/I
Signal waveform
Frequency
Voltage magnitude
Flicker
Unbalance (all channels)
Harmonic
Interharmonic
232
Type
Voltage
Capacity
Typical life
capacity
IP20
IP40 (with display, without door)
IP51 (with display and door)
IP2x
23 °C ± 2 °C
40 % to 60 % RH
V
PS
3
DC field:  40 A/m
AC field:  3 A/m
none
sinus
50 Hz ± 0.5 Hz
60 Hz ± 0.5 Hz
Udin ± 1 %
Pst < 0.1 %
100 % ± 0.5 % of Udin
0 % to 3 % of Udin
0 % to 0.5 % of Udin
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
PANASONIC CR2032 or
VARTA 6032 101 501
3 V
230 mAh
For operation with permanently applied
supply voltage:
10 years
For operation with sporadically interrupted
supply voltage:
a total of 2 months over a 10-year period
2 GB
± 1 %