Siemens SICAM Manual

Siemens SICAM Manual

Feeder condition monitor
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

SICAM
Feeder Condition Monitor
V03.30
Manual
E50417-H8940-C580-A4
Preface
Open Source Software
Table of Contents
Delivery
Introduction
Hardware Components and Drawings
Device Functions
Technical Data
Type Testing
Connection Diagrams
Parameterization
Modbus Registers
Glossary
Index
1
2
3
4
5
6
7
A
B

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SICAM

  • Page 1 Preface Open Source Software Table of Contents SICAM Delivery Feeder Condition Monitor Introduction Hardware Components and Drawings V03.30 Device Functions Manual Technical Data Type Testing Connection Diagrams Parameterization Modbus Registers Glossary Index E50417-H8940-C580-A4...
  • Page 2 Although including rights created by patent grant or registration of a Siemens AG has made best efforts to keep the document as utility model or a design, are reserved. precise and up-to-date as possible, Siemens AG shall not...
  • Page 3: Preface

    Preface Purpose of the Manual This manual describes the application, functions, installation, and operation of the SICAM Feeder Condition Monitor (FCM) 6MD232xx. Target Audience Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main- tenance of automation, selective protection and control equipment, and operational crew in electrical installa- tions and power plants.
  • Page 4 Fax: +49 (180) 524-2471 E-mail: support.energy@siemens.com Additional Support For questions about the system, please contact your Siemens sales partner. Training Courses Inquiries regarding individual training courses should be addressed to our Training Center: Siemens AG Siemens Power Academy TD Humboldtstraße 59 90459 Nürnberg...
  • Page 5 Used Symbols on Device Symbol Description Direct current, IEC 60417-5031 Alternating current, IEC 60417-5032 Direct and alternating current, IEC 60417-5033 Earth (ground) terminal, IEC 60417-5017 Protective conductor terminal, IEC 60417-5019 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 6 Description Caution, risk of electric shock Caution, risk of danger, ISO 7000-0434 Protective Insulation, IEC 60417-5172, Safety Class II devices Guideline 2002/96/EC for electrical and electronic devices Guideline for the Eurasian Market SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 7: Open Source Software

    License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years since purchase of the Product. We are liable for the Product including the Open Source Software contained in it pursuant to the license conditions applicable to the Product.
  • Page 8 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 9: Table Of Contents

    Ground-Fault Detection with Cos φ/Sin φ Measurement..........45 4.1.21 Determination of a Ground Fault with the Pulse-Location Detection Mechanism... 46 4.1.22 Determination of the Ground-Fault Phase..............49 4.1.23 Determination of Repeated Phase Faults with Automatic Reclosing ......49 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 10 Type Testing............................... 65 Type Testing........................66 Connection Diagrams..........................69 Connection Diagrams......................70 Installing the Device......................73 Sensor Connections......................74 Modbus Connection of SICAM FCM with RTU..............78 Parameterization............................81 Parameterization.......................82 Parameterizing the User Interface..................83 Editing the Device Settings....................91 Modbus Registers............................93 Modbus Registers......................94 Implementation of the Modbus Protocol ................95...
  • Page 11: Delivery

    Delivery Delivery SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 12: Delivery

    Do not throw the SICAM FCM device containing a battery into a fire. ² NOTE SICAM FCM with 1 contained lithium metal cell (0.6 g lithium content) meets the preconditions of Special Provision 188 of the UN Recommendations on the Transport of Dangerous Goods, 17th revised edition and is classified according to: •...
  • Page 13: Introduction

    Introduction Overview Environmental Protection Hints SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 14: Overview

    0.4 kV to 36 kV. SICAM FCM measures the RMS value for alternating voltage, alternating current, and power frequency. SICAM FCM calculates the active power (P), reactive power (Q), apparent power (S), power factor (cos φ), phase angle, energy, and other relevant values.
  • Page 15 As a simple power quality meter and energy measurements in various applications Flush Mounting SICAM FCM can be flush-mounted in the panel and operated inside an enclosed dry room. To mount SICAM FCM in the panel, proceed as follows: •...
  • Page 16 Voltage-Detection System (VDS) has to be ordered separately. Voltage-Detection System (VDS) Interface Cable • 4-wire connection lead with integrated protection circuit to connect 6MD2322-0AA80-0AB3 SICAM FCM 6MD2322-1AA00-1AA0/CC with the LRM voltage detection system • 1 ground input • Length: 0.3 m •...
  • Page 17 Accuracy class: 0.5 • IEC 60044-7 for asymmetric T connectors of nkt cables type CB-24 • Voltage factor: 1.2 V • Voltage factor: 1.9 V for maximum of 8 hours, GOST certificate SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 18 Refer to Table 2-1 – – – sensor ments In order to set up SICAM FCM (MLFB: 6MD2322-1AA00-1AA0/CC and above) with voltage-detection system, an appropriate connecting cable (MLFB: 6MD2322-0AA80-0AB3) must be used. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 19 The device with MLFB number 6MD2322-1AA00-1AA0/BB must be loaded with firmware V02.XX only. Accessories You can download the current version of the SICAM FCM manual from Siemens Powerquality. The ground current can also be calculated in isolated/compensated electrical power systems. Consider information regarding accu- racy.
  • Page 20: Environmental Protection Hints

    When disposing of or transferring a mobile storage device, Siemens strongly recommends physically destroying it or completely deleting data from the mobile storage device by using a commercially available computer data erasing software.
  • Page 21: Hardware Components And Drawings

    Hardware Components and Drawings Hardware Components Terminal Diagram Dimensional Drawings SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 22: Hardware Components

    FAULT (Red) Indicates when any distribution-system fault is detected – COM (Yellow) Indicates that the communication is active between Modbus master and the SICAM FCM – RUN (Green) Indicates the healthy condition of the device and operating on the auxiliary voltage •...
  • Page 23: Terminal Diagram

    (17) Phase current I (18) Neutral (19) Voltage input V (20) Neutral (21) Voltage input V (22) Neutral (23) Voltage input V (24) Neutral N, V N, V N are internally shorted SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 24 Screw connection Conductor size (solid) 1.0 mm Conductor size (stranded) 1.0 mm Stripping length 8.0 mm AWG (max.) 16.0 AWG (min.) 26.0 Torque 0.5 Nm Screwdriver size 3/32 inch or 2.5 mm SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 25: Dimensional Drawings

    This chapter shows the dimensional drawings and different views of the device. Rear View [le_sfcmrearview, 1, --_--] Figure 3-3 Rear View with Terminals Power supply Modbus Digital input Digital output 2 Digital output 1 Voltage input Current input SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 26 Hardware Components and Drawings 3.3 Dimensional Drawings Front View [dw_fcm_front, 1, en_US] Figure 3-4 Front View Isometric View [dw_fcm_iso_view, 1, en_US] Figure 3-5 Isometric View SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 27 Hardware Components and Drawings 3.3 Dimensional Drawings 1 A/5 A Adaptor Drawing [le_sfcm1aadap-231015, 1, --_--] Figure 3-6 1 A/5 A Adaptor Threaded stud CT adaptor PCB Cable assembly SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 28 [le_sfcm-capconncbl, 2, --_--] Figure 3-7 Connecting Cable of SICAM FCM SICAM FCM Connecting cable (6MD2322-0AA80-0AB3); necessary for 6MD2322-1AA00-1AA0 Orientation of connecting cable to SICAM FCM voltage-input terminals SICAM FCM voltage-input terminals Connecting cable (L , ground) Voltage-detection system SICAM, Feeder Condition Monitor, Manual...
  • Page 29: Device Functions

    Device Functions Description SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 30: Description

    The device uses the Definite Minimum Time (DMT) or Inverse Definite Minimum Time (IDMT) characteristics for detecting the fault. It identifies the type of the fault and also determines the direction. The following logic diagram shows the fault indication. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 31 NOTE For solid ground or if V is set to 0, V is disabled and only I (Watt-metric) is used for detecting the ground fault. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 32: Fault-Reset Mechanism

    NOTE For isolated/compensated systems in case of 2-phase-to-ground and 3-phase-to-ground faults, whenever a ground fault and phase fault occur at a same time, SICAM FCM indicates phase fault as a priority event on HMI/Modbus. For more information about direction determination, refer to 4.1.15 Determination of Fault...
  • Page 33: Enhanced Fault Validation And Fault-Reset Function

    6 kV or 5 A respectively. After elapse of the set time, the device resets the fault indication. The following logic diagrams illustrates the fault-detection initiation and fault reset. [lo_sfcmfaultdetect-reset, 2, en_US] Figure 4-4 Logic Diagram for Fault-Detection Initiation and Fault Reset SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 34 For solid ground or if V > is set to 0, V is disabled and only I (Watt-metric) is used for detecting the ground fault. The following logic diagram illustrates the fault indication and fault reset. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 35 Device Functions 4.1 Description [lo_sfcm_fltindrst, 2, en_US] Figure 4-6 Logic Diagram for Fault Indication and Fault Reset The following figure describes the timer-based fault-indication operation. [lo_medvolsup, 2, en_US] Figure 4-7 Timer-Based Fault Indication SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 36: Trip Time Dmt And Idmt

    IDMT characteristics are defined as Inverse because the trip time is inversely proportional to the fault current being measured. In SICAM FCM, the IDMT function supports the Normal Inverse (NI) characteristics. The ANSI codes supported by the IDMT function are non-directional (51) and directional (67) for overcurrent indication.
  • Page 37: Ground-Fault Parameter Active Group Setting

    The device sends the fault current, fault type, and additional fault information to the RTU. If a fault is detected, the red LED flashes every 1 s if the device is not powered through an auxiliary supply. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 38: Do Configuration

    SICAM FCM to improve system accuracy. • Sensors which are used in combination with SICAM FCM and do not have correction factors, disable the respective correction factors. In this way, the device works with secondary values as measured without any influence on magnitudes and phase angles.
  • Page 39: Power-Flow Direction Reversal

    4.1.12 The P,Q sign parameter is used to reverse the sign of active power (P) and reactive power (Q) for all phases. The P,Q sign parameter cannot be configured for individual phases. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 40: 3-Phase Angle Calculations

    The phase sequence of the measured phase-to-ground voltages is checked by monitoring the angle difference between phase-to-ground and phase-to-phase voltages. SICAM FCM monitors the phase sequence of voltage signals from voltage sensors and displays it on the HMI/ Modbus. The phase-sequence monitoring algorithm uses measured phase-to-ground voltage and phase-to- phase voltage angles in balanced condition.
  • Page 41: Determination Of Fault Direction

    If there are any device alerts and a fault is detected in the system, then the phase sequence is displayed as --- on the HMI and the Modbus register is set to 0. NOTE Protection functions implemented in SICAM FCM are designed for clockwise phase sequence only. Determination of Fault Direction 4.1.15 The fault direction for the phase faults is determined by calculating the phase angles between the fault current and the corresponding phase-to-phase voltages.
  • Page 42: Direction Determination Of Phase Elements

    The undetermined area for the device MLFB 6MD2321-1AA00-1AA0 is 10° and the respective angles change accordingly. The undetermined area for the device MLFB 6MD2322-1AA00-1AA0 is 20° and the respective angles change accordingly. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 43: Directional Ground Fault (Compensated/Resonant-Grounded)

    4th quadrant, then the direction is shown as forward. For more information about directional ground-fault parameters (isolated grounded), see Table A-3 and refer to the Fault Parameter > Ground-Fault Detection > Neutral-point Treatment menu. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 44: Ground-Fault Direction For Solidly Grounded System

    This results in determining the ground-fault direction based on the rotation angle of the reference vector. [dw_sfcm-grndflt-sol, 1, en_US] Figure 4-13 Ground-Fault Direction for Solidly Grounded System SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 45: Ground-Fault Detection With Cos Φ/Sin Φ Measurement

    [lo_sfcm-grndfltdet-cossine, 2, en_US] Figure 4-14 Logic Diagram for Ground-Fault Detection with Cos φ/Sin φ Measurement Method The following table displays the I range and the ground-fault detection with cos φ/sin φ measurement method status: SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 46: Determination Of A Ground Fault With The Pulse-Location Detection Mechanism

    When the capacitor is switched on, an additional capacitive ground current is generated and the ground- current compensation changes. • When the capacitor is switched off, the additional capacitive ground current no longer exists and the ground-current compensation returns to the normal state. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 47 Using different values of the parameters Pulse-on duration (TPulse ON) and Pulse-off duration (TPulse OFF), the differentiation between healthy and faulty feeders for high-impedance ground faults can be ascertained. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 48 TPulse OFF, then a valid pulse is detected. If the number of detected pulses within the pulse monitoring time reaches the setting of the Number of Pulses for Operate (PulseTh Op.), then the ground fault is detected. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 49: Determination Of The Ground-Fault Phase

    The device detects and records the repeated phase faults. A repeated phase fault is defined as the phase fault that occurs due to an automatic reclosing (AREC) as long as the SICAM FCM indicates the fault, that is, it has not been reset via one of the possible reset mechanisms yet.
  • Page 50: Inrush-Current Detection/Blocking

    The inrush current is detected by analyzing the magnitude of the 2nd harmonic components of the phase vectors. [lo_sfcm-inrushcrnt-dct, 2, en_US] Figure 4-18 Inrush-Current Detection Logic Diagram SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 51: Primary Current Settings

    When the ground-current calculation is used with the vector method, the deviation of the calculated ground current is 3 %. For more information about ground-current calculation, refer to Ground-Current Acquisition, Page 122 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 52: Network Voltage Ratio

    Device Functions 4.1 Description NOTE For higher accuracy, Siemens recommends measuring the ground current in compensated/isolated systems. Network Voltage Ratio 4.1.28 In the medium-voltage applications, higher rated voltage sensors can be used in the system with lower rated voltages. For example, a 20-kV sensor can be used in a 10-kV primary voltage system. In this case, enter the...
  • Page 53: Low-Voltage Measurement

    The device is able to detect the direction of phase faults and ground faults in solidly grounded MV networks. The primary voltages affected by transformer losses can be corrected by providing an offset in the Primary voltage correction parameter. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 54: Voltage Measurement Via Integrated Voltage-Detecting Systems

    (VDS) with low resistance modified (LRM) inter- face. Both the SICAM FCM and VDS device are connected in parallel connections. For the current measure- ments, the inputs are provided via LoPo sensors or CT adaptor.
  • Page 55: Energy Measurement

    The device needs a time synchronization, when it resumes from the sleep mode to ensure the correct time and date. Also the time synchronization is required when the device is powered on after 8 hours of sleep mode. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 56: Remote Firmware Updates

    Remote Firmware Updates 4.1.35 The firmware can be updated remotely via the Modbus/RS485 interface when it is connected to SICAM CMIC RTU. The firmware update is only possible with baud rates ranging from 4800 bps to 19200 bps. For more information, refer to the following CMIC RTU documents: •...
  • Page 57: Device Alerts

    Warning). The threshold is defined in percentage of rated primary voltage. For more information about the overvoltage alarm and overvoltage warning, see Table A-4 and refer to the Fault Parameters > Over- voltage Warning and Overvoltage Alarm menu. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 58: Archive Logging

    The minimum and maximum values of current are archived every 15 minutes, 30 minutes, 45 minutes, 1 hour, 24 hours, 1 month, and 1 year. For more information about the parameters of archive logging, see Table A-1 and refer to the Events and Trailing Pointers menus. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 59: Battery Freshness Mode

    Home Screen. [dw_sfcmbfmbf-140314, 2, en_US] Figure 4-27 Battery Freshness The Remove Power Source menu appears. As displayed in the Remove Power Source menu, disconnect the auxiliary voltage to enable the BFM ² mode. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 60 If the device is powered OFF without enabling the Battery Freshness Mode, then: • Device HMI displays the message Battery is being discharged, enable battery freshness mode and • The Fault LED (Red) and Communciation LED (Yellow) flash for 30 min. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 61: Technical Data

    Technical Data Device Technical Data SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 62: Device Technical Data

    1 % for a duration of 1 h For optimum battery capacity, Siemens recommends storing the device below 30 °C; 30 % RH The accuracy of voltage measurements is up to 0.5 % (±10 % of the rated voltage) for MLFB 6MD2321-1AA00-1AA0.
  • Page 63 Baud rate (bps) 2400, 4800, 9600, 19200, 38400, 57600, 115200 Default value: 115 200 bps Data format 8N1, 8E1, 8O1 Default value: 8N1 Supported address area 1 to 247 Default value: 247 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 64 In the low-power mode, you can reset a fault, set parameters, and view events/records. In this mode, meas- urements, fault detection, and communication functions are not available. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 65: Type Testing

    Type Testing Type Testing SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 66: Type Testing

    Table 6-2 Humidity Permissible humidity 95 % relative humidity Siemens recommends installing the devices in a place where they are not exposed to direct sunlight or great temperature variations that could lead to condensation. Electrical Tests Table 6-3 Safety Tests...
  • Page 67 Voltage dips and IEC 61000-4-11, 0 %, 40 %, and 70 % dips on AC/DC power supply interruptions IEC 61000-4-29, 0 % short interruptions for 250/300 cycles (50 Hz/60 Hz) IEC 61326-1 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 68 CISPR 32 1 GHz to 6 GHz Ingress Protection of Enclosure Table 6-7 Ingress Protection Tests Standard Test Requirements Degree of protection IEC 60529 IP40 for front side IP20 for rear side SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 69: Connection Diagrams

    Connection Diagrams Connection Diagrams Installing the Device Sensor Connections Modbus Connection of SICAM FCM with RTU SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 70: Connection Diagrams

    The device can be used as a dedicated Fault Passage Indicator (FPI) by using only the 3 current inputs. No directional fault information is provided in this scheme. [dw_sfcm-sfpi, 2, en_US] Figure 7-1 SICAM FCM as Fault Passage Indicator NOTE In this connection scheme, the accuracy of ground-current measurements cannot be guaranteed for isolated/resonant ground connection.
  • Page 71 [dw_sfcm-fltdtct-lopovt, 2, en_US] Figure 7-3 SICAM FCM as Fault Detector – 3 Low-Power Voltage Sensors and Current Sensors with 3 Phase Currents for MLFB 6MD2321-1AA00-1AA0 In a medium-voltage system, the device is connected to the voltage inputs V...
  • Page 72 [dw_sfcm-fltdtct-ressnt, 2, en_US] Figure 7-5 SICAM FCM as Fault Detector – 3 Low-Power Voltage Sensor with 2 Phase Currents and Sensi- tive Ground-Current Sensor for MLFB 6MD2321-1AA00-1AA0 In a medium-voltage system, the device is connected to the voltage inputs V...
  • Page 73: Installing The Device

    Ensure that the terminal 1 of the device is properly grounded with the ground wire provided. NOTE If the device is commissioned after a long period of time, make sure to run a power ON-OFF sequence and keep the device in the OFF condition for an hour. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 74: Sensor Connections

    The following table shows how the current and voltage sensors are designated as per the terminals. [dw_sfcmtrml, 2, en_US] Figure 7-7 Terminal Diagram [ph_current_sensor_wires, 1, --_--] Figure 7-8 Phase-Current Sensors Cable Leads (Red/Black) [ph_voltage_sensor_wires, 1, --_--] Figure 7-9 Phase-Voltage Sensors Cable Leads (Black/Brown) SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 75 Power-Flow Direction Parameters for Solidly-Grounded Systems Phase Parameter Value power-flow direction Not reversed power-flow direction Not reversed power-flow direction Not reversed Table 7-3 describes the power-flow direction parameters for the isolated/compensated-grounded systems. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 76 Reversed power-flow direction Not reversed NOTE Table 7-2 Table 7-3 show the settings recommended by Siemens. You can change the power-flow direction according to your applications. Current-Sensors Grounding Connection [dw_sfcm_cursen_grndconn, 1, en_US] Figure 7-11 Current-Sensors Grounding Connection SICAM, Feeder Condition Monitor, Manual...
  • Page 77 Figure 7-12 Voltage Sensors Grounding Connection NOTE Always ensure that the protective ground (terminal 1) of SICAM FCM is grounded in the RMU panel with a short cable size ≥ 2.5 mm SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 78: Modbus Connection Of Sicam Fcm With Rtu

    Connection Diagrams 7.4 Modbus Connection of SICAM FCM with RTU Modbus Connection of SICAM FCM with RTU The following figure shows how the RS485 port of SICAM FCM is connected with the Remote Terminal Unit (RTU). [dw_connection_fcm-rtu, 1, en_US] Figure 7-13...
  • Page 79 Connection Diagrams 7.4 Modbus Connection of SICAM FCM with RTU Modbus Connection The following figure shows the Modbus connection with SICAM CMIC/A8000, SICAM FCM, and the Motor Control Unit (MCU). [dw_modbus_connection_fcm-mcu, 2, en_US] Figure 7-14 Modbus Connection with SICAM FCM and MCU The following S2 DIP switch settings show the mode of operation of RS485 on MCU.
  • Page 80 Figure 7-16 Modbus Termination NOTE SICAM FCM has no internal Modbus load resistor. If SICAM FCM is located at the end of the Modbus connec- tion, use an external resistor for Modbus termination. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 81: A Parameterization

    Parameterization Parameterization Parameterizing the User Interface Editing the Device Settings SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 82: Parameterization

    The up and down arrow is used to move the cursor. It is also used to scroll within the menu list and for selecting or entering numerical values. You can also parameterize the device using the SICAM FCM Configurator tool. For more information, refer to the SICAM FCM Configurator Manual.
  • Page 83: Parameterizing The User Interface

    3-phase reactive power • 3-phase apparent power • Phase sequence • Zero sequence voltage • Positive-sequence voltage • Negative-sequence voltage The default menu also displays the power-flow direction and status of the feeder. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 84 [dw_sfcmdefscreen, 2, en_US] Figure A-2 Default Menu Parameterization Menu Structure The parameterization menu structure displays the main menu and the relevant submenu functions. Table A-1 Parameters Menu Structure MENU ▶ EVENTS ▶ TRAILING POINTERS SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 85 0.04 s to 60 s DETECTION tI > ▶ SAVE ▶ THRESHOLD ▶ 0 % to 100 % SETTING V > (Set to "0", the ground-fault detection is based on I >) ▶ SAVE SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 86 0.50 s to 20 s DETEC- (Set to "0" to disable the TION detection function) ▶ SAVE ▶ TPULSE OFF ▶ 0.50 s to 20 s (Set to "0" to disable the detection function) ▶ SAVE SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 87 (Set to "0" to disable the overcurrent alarm) ▶ SAVE ▶ AUTO RESET ▶ 0 min to 480 min TIME (Set to "0", auto reset is immediate on fault restoration) ▶ SAVE SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 88 VOLTAGE ▶ SAVE ▶ SENSOR VOLTAGE ▶ 1.0 kV to 36.0 kV PRIMARY ▶ SAVE ▶ VOLTAGE CORREC- ▶ MAGNITUDE TION FACTOR FACTOR ▶ ANGLE OFFSET ▶ MAGNITUDE FACTOR ▶ ANGLE OFFSET SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 89 COUNTER RESET ▶ ▶ P, Q SIGN ▶ NOT REVERSED ▶ REVERSED ▶ SAVE Table A-6 Parameters Menu Structure - DO Configuration DO CONFIGURATION ▶ FAULT DIRECTION OR DEVICE HEALTH ▶ SAVE SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 90 • Frequency • Neutral-point treatment • Baud rate • Parity • Ground-fault detection I >, when the parameter is changed above or below the threshold of 1 A • Ground-current acquisition (calculation/measurement) SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 91: Editing The Device Settings

    Press Esc if you want to cancel the edit mode and to return to the display mode. All the saved values are ² discarded. [dw_sfcmeditparaset, 1, en_US] Figure A-3 Editing Phase-Protection Settings SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 92 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 93: B Modbus Registers

    Implementation of the Modbus Protocol Bit-Type Data Register-Type Data – Holding Registers Register-Type Data – Input Registers Register-Type Data – Analog Input Registers Register-Type Data - Events Register-Type Data – Trailing Pointers Self-Test Mode SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 94: Modbus Registers

    • 8-bit data bytes • Error checking The following Modbus data models are supported: • Bit type data – Discrete input – Coil • Register-type data – Input register – Holding register SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 95: Implementation Of The Modbus Protocol

    Modbus Parameters Modbus ID 1 to 247 0 - Broadcast 248 to 255 Special Modbus type In the SICAM FCM, the data-byte standard setting is as follows: • 1 start bit • 8 data bits (LSB first) • 1 parity bit (odd/even/none) •...
  • Page 96 Discrete Input Overcurrent alarm Discrete Input Overcurrent stage I>, low-set without direction indication Discrete Input Phase-fault indication (I>/I>>) Discrete Input Phase-fault indication (I>/I>>) for at least 3 s Discrete Input Device-health status SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 97: Register-Type Data - Holding Registers

    0, 50 to 2500 Overcurrent trip value I>, low-set uInt16 0, 4 to 6000 Overcurrent response time (tI>), low-set x 10 ms uInt16 0, 1 to 60 uInt16 0, 1 to 25 uInt16 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 98 Over-voltage phase threshold for ground uInt16 fault V> 0, 1 to 300 3I0 Delta pulse off-on uInt16 0, 20 to 2000 Pulse-on duration x10 ms uInt16 0, 20 to 2000 Pulse-off duration x10 ms uInt16 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 99: Register-Type Data - Input Registers

    For more information about register-type data – input registers, see B.5 Register-Type Data – Input Registers. Default values in holding addresses 80 to 91 are dependent on whether the parameter Correction factor (holding register 79) is disa- bled or enabled. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 100 1/100 kV for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor 1011 0 to 3599 Phase angle I 1/10° uInt16 1012 0 to 3599 Phase angle I 1/10° uInt16 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 101 100/√3 sensor, and for 400/√3 sensor 1039 -32768 to 32767 3-phase reactive power 1/10 kVAr for 230-V sInt16 sensor 1/100 MVAr for 3.25/ √3 sensor, for 100/√3 sensor, and for 400/√3 sensor SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 102 100/√3 sensor, and for 400/√3 sensor 1053 0 to 65535 Firmware major and maintenance version – uInt16 number 1054 0 to 65535 Application firmware and build version – uInt16 number SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 103 Undervoltage warning time (hours and h and min uInt16 minutes) – Undervoltage warning time (month and month and date uInt16 date) – Undervoltage warning time (year) year uInt16 – Overcurrent alarm type – uInt16 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 104 03. The modified values contained in the registers are saved during a device reset. For more information about register-type data - trailing pointers, see B.8 Register-Type Data – Trailing Pointers. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 105 215 to 217 (min) 24 hours 218 to 221 Inp-Reg (max) 24 hours uInt16 222 to 224 (max) 24 hours 225 to 227 (max) 24 hours 228 to 230 (max) 24 hours SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 106 267 to 269 (min) 1 year 270 to 273 Inp-Reg (max) 1 year uInt16 274 to 276 (max) 1 year 277 to 279 (max) 1 year 280 to 282 (max) 1 year SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 107: Bit-Type Data

    >) > indication detected No I > indication occurred Overvoltage warning (V Overvoltage warning detected Warning) No overvoltage warning detected Overvoltage alarm (V Alarm 1 Overvoltage alarm detected No overvoltage alarm detected SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 108 No I overcurrent indication detected overcurrent (I>/I>>) indica- overcurrent indication detected tion No I overcurrent indication detected overcurrent (I>/I>>) indica- overcurrent indication detected tion No I overcurrent indication detected SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 109 No intermittent ground fault detected (I >) Phase-sequence monitoring Clockwise phase sequence, ABC detected ACB or no phase sequence detected Phase-sequence monitoring Counter-clockwise phase sequence, ACB detected ABC or no phase sequence detected SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 110: Register-Type Data - Holding Registers

    (Address 5 to 8) The format used for date and time complies with EN60870-5- 4:1993. It consists of 4 succes- sive registers for writing in one request. It uses the function code 16. (Address 5) SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 111 Date and Time – Date/Month Not used Month Not used Date Month Format 4-bit unsigned integer Unit Month Range 1 to 12 Date Format 5-bit unsigned integer Unit Date Range 1 to 31 (Address 8) SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 112 For example, if Modbus value is: 10 = 1.0 kV 115 = 11.5 kV Overcurrent Trip Value (I>>), high-set (Address 11) This register defines the trip value for overcurrent detection for short circuits. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 113 (Address 14) This register defines the minimum time required for a ground fault to exist and to allow the device to indicate a fault. Format 16-bit unsigned integer Unit Range 4 to 6000 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 114 1 = Deutsch 2 = Español 3 = Portugués 4 = Français Default 1 = Deutsch Voltage-Transformer Secondary/Low-Power Voltage Transformer (Address 18) This register contains the selected low-power voltage transformer/voltage-transformer secondary voltages. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 115 0 = 12 hour format Alarm (Address 21) This register defines the maximum threshold voltage you can set for providing an alarm. It is expressed in percentage (%) of the primary voltage. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 116 0 % to 30 % of the primary voltage When 0 is selected, then the function is disabled. Default Neutral-Point Displacement Time tV > (Group 1) (Address 26) This register defines the neutral-point displacement time. It is expressed in milliseconds. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 117 (Address 28) This register defines the rated primary current. Format 16-bit unsigned integer Unit Range 50 to 1000 Default Overcurrent Trip Value (I>), Low-Set (Address 29) This register defines the trip value for overcurrent (low-set) detection for short circuits. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 118 (Address 32) This register defines the absence of voltage and current monitoring time. Format 16-bit unsigned integer Unit Range 0, 1 to 25 Default Timer (T3) (Address 33) This register defines the time for auto reset after resumption of voltages and currents. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 119 When 0 is selected, then the I warning is disabled. Alarm Time Setting (Address 36) This register defines the overcurrent alarm time. The value is expressed in minutes. Format 16-bit unsigned integer Unit Range 1 to 120 Default SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 120 330° with respect to the MV system. (Group 1) (Address 40) This register defines the value of ground current for ground-fault detection using the cos φ/sin φ method. The value is expressed in amperes. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 121 (Address 44) This register defines the minimum time required for a ground fault to exist and to allow the device to indicate a fault. Refer to Ground-Fault Response Time (tI >) (Group 1) , Page 113. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 122 If the ground-current sensor is not used for isolated/resonant-ground connec- tion, the ground current is calculated. Not used Not used Not used Not used Not used Not used Not used Not used SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 123 (Address 54) This register defines the time threshold for blocking of fault indication by inrush-current detec- tion. It is expressed in milliseconds. Format 16-bit unsigned integer Range 0 to 60 000 Unit Default Ground Sensor (Address 55) This register defines the value of the ground-current sensor ratio. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 124 1 = Reversed Power-Flow Direction (Address 58) This register defines the I power-flow direction parameter. Format 16-bit unsigned integer Range 0 to 1 0 = Not reversed 1 = Reversed Unit – SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 125 (Address 61) Reserved for future use (Address 62) Reserved for future use (Address 63) Reserved for future use (Address 64) Reserved for future use (Address 65) Reserved for future use (Address 66) SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 126 Unit percentage Default Pulse-on Duration (TPulse On) (Address 73) This register defines the duration of the pulse ON, in other words the switch-on duration of the capacitor. It is expressed in milliseconds. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 127 Unit – Range 1 to 100 Default Number of Pulses for Monitoring (PulseTh Mon.) (Address 76) This register defines the number of pulses to be considered for calculating the pulse monitoring time. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 128 (Address 79) This register provides an option to enable or disable the correction factor for voltage and current measurements. Format 16-bit unsigned integer Unit – Range 0 to 1 Default Magnitude Factor (Address 80) This register defines the correction factor for the V magnitude. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 129 (Address 86) This register defines the correction factor for the I magnitude. Format 16-bit unsigned integer Unit 1/1000 Range 0, 800 to 1200 Default (correction factor disabled) 0 Default (correction factor enabled) 1000 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 130 (Address 90) This register defines the correction factor for the I magnitude. Refer to Magnitude Factor, Page 129. Angle Offset (Address 91) This register defines the correction factor for the I angle. It is expressed in minutes (min). Angle Offset, Page 130. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 131: Register-Type Data - Input Registers

    For example, if Modbus value is: 40 = 0.4 A 600 = 6 A Refer to Phase Current I , Page 131. Voltage V (Address 1004) This register contains the actual voltage V SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 132 V1. Format 16-bit unsigned integer Unit 1/10° Range 0 to 3599 For example, if Modbus value is: 905 = 90.5° The value is indicated in steps of 1/10°. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 133 (Address 1021) This register contains the phase angle V with reference to the voltage V1. Refer to Phase Angle I , Page 132. Apparent Power Phase 1 (Address 1022) This register contains the apparent power phase 1. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 134 (Address 1024) This register contains the reactive power phase 1. Format 16-bit signed integer Unit 1/10 kVAr for 230-V sensor 1 kVAr for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 135 Refer to Reactive Power Phase 1, Page 134. Power Factor Phase 2 (Address 1030) This register contains the power factor phase 2. Refer to Power Factor Phase 1 (Cos φ ), Page 135. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 136 (Address 1037) This register contains the power-flow direction of phase I Refer to Power-Flow Direction of Phase I , Page 136. 3-Phase Active Power (Address 1038) This register contains the 3-phase active power. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 137 1000 = 10 MVA for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor 3-Phase Power Factor (Address 1041) This register contains the 3-phase power factor. Format 16-bit unsigned integer Unit 1/1000 Range -1000 to 1000 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 138 3-Phase Apparent Power (Address 1044) This register contains the 3-phase apparent power. Format 16-bit unsigned integer Unit 1/10 kVA for 230-V sensor 1 kVA for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 139 1 MWh for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor Range -2147483648 to 2147483647 For example, Modbus value is: 1000 = 1000 kWh for 230-V sensor 1000 = 1000 MWh for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 140 1000 = 1000 MVArh for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor Firmware Major and Maintenance Version Number (Address 1053) This register contains the firmware major and maintenance version number. Firmware major and maintenance version number Firmware major and maintenance version number SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 141 Unit Range 0 to 65535 Ground-Fault Status Register (Address 1057) This register contains the ground-fault status. Not used Not used Not used Not used Not used Not used Not used Not used SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 142 Phase Current I (Address 1060) This register contains the phase current I Refer to Phase Current I , Page 142. Ground Current I (Address 1061) This register contains the actual ground-current value I SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 143 Modbus Registers B.5 Register-Type Data – Input Registers Format 16-bit unsigned integer Unit 1/10 A Range 0 to 65535 For example, if Modbus value is: 40 = 4 A 600 = 60 A SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 144: Register-Type Data - Analog Input Registers

    Range 0 to 23 Format 8-bit unsigned integer Unit Range 0 to 59 Last Reset Time (Month and Date) (Address 4) This register contains the last reset time in month and date. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 145 Not used Format 16-bit unsigned integer Unit – Range – Overvoltage Alarm Time (Milliseconds) (Address 7) This register contains the alarm time in milliseconds. Refer to Last Reset Time (Milliseconds), Page 144. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 146 (Address 16) This register defines the phase in which the undervoltage alarm is occurred. Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 147 (Address 24) This register contains the undervoltage warning time in month and date. Refer to Last Reset Time (Month and Date), Page 144. Undervoltage Warning Time (Year) (Address 25) This register contains the undervoltage warning time in years. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 148 Last Reset Time (Milliseconds), Page 144. Overcurrent Warning Time (Hours and Minutes) (Address 33) This register contains the overcurrent warning time in hours and minutes. Refer to Last Reset Time (Hours and Minutes), Page 144. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 149 Refer to Last Reset Time (Month and Date), Page 144. Overcurrent Warning Time (Year) (Address 35) This register contains the overcurrent warning in years. Refer to Last Reset Time (Year), Page 145. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 150: Register-Type Data - Events

    (Address 302, 312, …., 492) This register contains the time in milliseconds. Milliseconds Milliseconds Format 16-bit unsigned integer Unit Range 0 to 59999 Time in Hours and Minutes (Address 303, 313, …., 493) This register contains the time in hours and minutes. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 151 Not used Not used Not used Not used Year Format 7-bit unsigned integer Unit Year Range 12 to 99 For example, if Modbus value is: 12 = Year 2012 99 = Year 2099 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 152 16-bit unsigned integer Unit 1/10 A for solid and isolated/resonant connection Range 0 to 9999 for solid connection 0 to 65535 for isolated/resonant connection Reserved (Address 310 to 500) These registers are reserved. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 153: Register-Type Data - Trailing Pointers

    B-16) This register contains the minimum values and the maximum values of the phase current I measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively. Refer toPhase Current I , Page 153. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 154 1 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively. Format 16-bit signed integer Unit 1/10 kVAr for 230-V sensor 1 kVAr for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor Range -32768 to 32767 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 155 B-16) This register contains the minimum values and the maximum values of the apparent power for phase 3 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively. Refer to Apparent Power S1 for Phase 1, Page 155. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 156: Self-Test Mode

    Modbus Registers B.9 Self-Test Mode Self-Test Mode In SICAM FCM, the self-test mode feature can be enabled during the commissioning and when required. The self-test mode is activated via any of the following: • • RS485/Modbus interface During the self-test mode, the device changes the values of all Modbus registers and provides an option for the user to verify the Modbus registers in a sequential order as per the defined-time interval.
  • Page 157 Phase-fault indication (I>/I>>) for at least 3 s Device-health status I>/I>> I>/I>> I>/I>> Ground fault phase 1 Ground fault phase 2 Ground fault phase 3 Intermittent ground fault Phase-sequence monitoring (ABC) Phase-sequence monitoring (ACB) SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 158 Power-flow direction phase 1 7777 1036 Power-flow direction phase 2 8888 1037 Power-flow direction phase 3 9999 1038 3-phase active power 3222 1039 3-phase reactive power 3444 1040 3-phase apparent power 3555 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 159 Analaog Input Register: Overvoltage/Undervoltage/Overcurrent Alarm and Warning Modbus Register Address Parameter Individual Test Value Last_Reset_Type Last_Reset_Time_SS Last_Reset_Time_HH_MM Last_Reset_Time_MO_DD Last_Reset_Time_YY OV_Alarm_Type OV_Alarm_Time_SS OV_Alarm_Time_HH_MI OV_Alarm-Time_MO_DD OV_Alarm_Time_YY OV_Warning_Type OV_Warning_Time_SS OV_Warning_Time_HH_MI OV_Warning_Time_MO_DD OV_Warning_Time_YY UV_Alarm_Type UV_Alarm_Time_SS UV_Alarm_Time_HH_MI UV_Alarm-Time_MO_DD SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 160 TP_I _Min_15_Minutes TP_I _Min_15_Minutes TP_I _Min_15_Minutes TP_P1_Min_15_Minutes TP_P2_Min_15_Minutes TP_P3_Min_15_Minutes TP_Q1_Min_15_Minutes TP_Q2_Min_15_Minutes TP_Q3_Min_15_Minutes TP_S1_Min_15_Minutes TP_S2_Min_15_Minutes TP_S3_Min_15_Minutes TP_I _MAX_15_Minutes TP_I _Max_15_Minutes TP_I _Max_15_Minutes TP_I _Max_15_Minutes TP_P1_Max_15_Minutes TP_P2_Max_15_Minutes TP_P3_Max_15_Minutes TP_Q1_Max_15_Minutes TP_Q2_Max_15_Minutes TP_Q3_Max_15_Minutes TP_S1_Max_15_Minutes TP_S2_Max_15_Minutes TP_S3_Max_15_Minutes SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 161 TP_Q1_Max_30_Minutes TP_Q2_Max_30_Minutes TP_Q3_Max_30_Minutes TP_S1_Max_30_Minutes TP_S2_Max_30_Minutes TP_S3_Max_30_Minutes TP_I _Min_45_Minutes TP_I _Min_45_Minutes TP_I _Min_45_Minutes TP_I _Min_45_Minutes TP_P1_Min_45_Minutes TP_P2_Min_45_Minutes TP_P3_Min_45_Minutes TP_Q1_Min_45_Minutes TP_Q2_Min_45_Minutes TP_Q3_Min_45_Minutes TP_S1_Min_45_Minutes TP_S2_Min_45_Minutes TP_S3_Min_45_Minutes TP_I _Max_45_Minutes TP_I _Max_45_Minutes TP_I _Max_45_Minutes TP_I _Max_45_Minutes TP_P1_Max_45_Minutes SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 162 TP_I _Max_60_Minutes TP_I _Max_60_Minutes TP_I _Max_60_Minutes TP_I _Max_60_Minutes TP_P1_Max_60_Minutes TP_P2_Max_60_Minutes TP_P3_Max_60_Minutes TP_Q1_Max_60_Minutes TP_Q2_Max_60_Minutes TP_Q3_Max_60_Minutes TP_S1_Max_60_Minutes TP_S2_Max_60_Minutes TP_S3_Max_60_Minutes TP_I _Min_24_Hours TP_I _Min_24_Hours TP_I _Min_24_Hours TP_I _Min_24_Hours TP_P1_Min_24_Hours TP_P2_Min_24_Hours TP_P3_Min_24_Hours TP_Q1_Min_24_Hours TP_Q2_Min_24_Hours TP_Q3_Min_24_Hours TP_S1_Min_24_Hours SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 163 TP_P1_Min_1_Month TP_P2_Min_1_Month TP_P3_Min_1_Month TP_Q1_Min_1_Month TP_Q2_Min_1_Month TP_Q3_Min_1_Month TP_S1_Min_1_Month TP_S2_Min_1_Month TP_S3_Min_1_Month TP_I _Max_1_Month TP_I _Max_1_Month TP_I _Max_1_Month TP_I _Max_1_Month TP_P1_Max_1_Month TP_P2_Max_1_Month TP_P3_Max_1_Month TP_Q1_Max_1_Month TP_Q2_Max_1_Month TP_Q3_Max_1_Month TP_S1_Max_1_Month TP_S2_Max_1_Month TP_S3_Max_1_Month TP_I _Min_1_Year TP_I _Min_1_Year TP_I _Min_1_Year SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 164 Phase current I Ground current I Reserved Event type (EVENT 1) Time in ms Time in hh and mm Time in dd and month Time in year Phase current I Phase current I SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 165 Time in ms Time in hh and mm Time in dd and month Time in year Phase current I Phase current I Phase current I Ground current I Reserved Event type (EVENT 6) SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 166 Phase current I Phase current I Phase current I Ground current I Reserved Event type (EVENT 10) Time in ms Time in hh and mm Time in dd and month Time in year SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 167 Event type (EVENT 14) Time in ms Time in hh and mm Time in dd and month Time in year Phase current I Phase current I Phase current I Ground current I SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 168 Time in dd and month Time in year Phase current I Phase current I Phase current I Ground current I Reserved Event type (EVENT 19) Time in ms Time in hh and mm SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 169 NOTE Enable the self test after ensuring that there is no fault condition exists. During the self-test mode duration if any fault occurs, the fault conditions are not updated in the device. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 170 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 171: Glossary

    The ring main unit is a modular extendable metal-clad switchgear designed primarily for the distribution appli- cations. RS485 interface The RS485 interface is a standard for digital, wire-based, differential, and serial data transmission. SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 172 Glossary A real-time clock is a computer clock or an integrated circuit that tracks the current time. Voltage-Detecting Systems SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 173: Index

    IMaxwarning time setting 120 Directional ground fault 43 Input registers 100 DO Configuration 38 Inrush-current detection/blocking 50 Intermittent ground fault 49 Isometric view 25 Environment 64 Event counter 150 Event type 150 Keypads 22 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...
  • Page 174 114 Parameterization menu structure 84 Parameters 22 Phase-Sequence Monitoring 40 PLC 94 Power consumption 64 Power factor 14 Primary voltage 112 Primary-Voltage Correction 120 Protection device class 64 Pulse-location detection 46 SICAM, Feeder Condition Monitor, Manual E50417-H8940-C580-A4, Edition 03.2019...

Table of Contents