Siemens SICAM Q100 7KG95 Series Manual page 60

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Basic Functions
2.5 Ethernet Communication
For the diagnosis of the IEC 61850 protocol in the Maintenance tab, proceed as follows:
In the navigation window, click IEC 61850 protocol.
[sc_q100_IEC61850_diagnosis, 1, en_US]
Figure 2-26
Parameter
With IEC 61850, the following parameters are displayed:
Voltage – Dead band: 5 % by default
Current – Dead band: 5 % by default
Voltage unbalance – Dead band: 5 % by default
Current unbalance – Dead band: 5 % by default
Power – Dead band: 5 % by default
Power factor – Dead band: 5 % by default
Frequency – Dead band: 0.05 % by default
Angle – Dead band: 0.5 % by default
Status
With IEC 61850, the following status is displayed:
IEC 61850 Communication status: OK or Fail
Port number: Set port number, for example 102
Information
With IEC 61850, the following information is displayed:
IED Name: SICAM
IEC 61850 Edition: 2
60
Maintenance Tab, Diagnosis IEC 61850
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021