Commissioning and First Steps
11.11 Connection Principle
Example: 3-Wire Network, 2 Voltage Transformers and 3 Current Transformers, Unbalanced
[dw_3-wire-network-3x-current, 1, en_US]
Figure 11-14
NOTICE
The secondary voltage on terminal F (voltage) must not exceed AC 600 V (AC 347 V for UL).
Non-observance can cause material damage.
Make sure that the maximum permissible phase-to-ground voltage (PE) is not exceeded.
²
Example: 4-Wire Network, 1 Voltage Transformer and 1 Current Transformer, Balanced
[dw_4-wire-balance, 1, en_US]
Figure 11-15
298
Example: 3-Wire Network, 2 Voltage Transformers and 3 Current Transformers, Unbalanced
Example: 4-Wire Network, 1 Voltage Transformer and 1 Current Transformer, Balanced
SICAM, SICAM Q100 7KG95xx, Manual