1.2
Device Overview
It is a multifunctional device for detection, calculation, recording, evaluation, display, and transmission of
measured electrical quantities with the following properties:
Device Properties
All devices consistently provide the following properties:
•
Device type:
–
Class A Power Quality Instrument and Power Monitoring Device, with measured-value recorders and
exchangeable 2 GB microSD card
–
Panel flush-mounting device with display for measured values and parameterization
–
Plastic case 96 mm/3.78 inch x 96 mm/3.78 inch x 100 mm/3.94 inch (W x H x D)
–
Web server for parameterization, visualization, and data management
–
Transmitting measured values using communication protocols
–
Degree of protection:
–
Front: IP40 (standard)
–
Terminals: IP20 (behind switch panel)
•
Input and output circuits:
–
4 inputs for alternating voltage measurements
–
4 inputs for alternating current measurements
–
2 binary inputs, for example, for synchronization pulses of the load profile or external triggers
–
2 binary outputs (relay contacts)
•
Measurement acc. to standard IEC 61000-4-30 Ed. 3, class A
•
Measured quantities:
–
Voltage V
–
Current I
–
Phase angle φ
–
System frequency f (fundamental)
–
10-s frequency
–
Active power P (accuracy class 0.2S; ANSI C12.20 current class 2 and current class 10)
–
Reactive power Q
–
Apparent power S
–
Energy measured values W
–
Active power factor cos φ
–
Power factor PF
–
Voltage and current harmonics up to 50th, voltage and current interharmonics up to 49th
–
THDS
–
Flicker acc. to IEC 61000-4-15
–
Mains signaling voltage
–
Harmonics phase angles, harmonic power
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Introduction
1.2 Device Overview
19