Measuring and Recording
3.1 General Information on Measuring and Recording
3.1
General Information on Measuring and Recording
Measuring System
3.1.1
The device measures the power quality according to IEC 61000-4-30 Ed. 3 in 1-phase or polyphase energy
supply systems.
The basic measuring interval for calculation of the following values is 10 cycles in 50-Hz systems or 12 cycles
in 60-Hz systems:
•
Voltage RMS values
•
Harmonics and interharmonics of voltages
•
Voltage unbalance
•
Currents
•
Harmonics and interharmonics of currents
NOTE
i
i
Depending on parameter settings, the browser displays the measured values with the corresponding unit
or indications in a table that is updated every 10 s. Harmonics and interharmonics can be represented in a
table or in a diagram.
The measuring functions are divided into the following parts:
•
PQ measurements
•
Operational measurements
•
Energy management and counter functions
An overview of the measured quantities demanded according to IEC 61000-4-30 Ed.3, their measurement
uncertainty and measuring ranges are represented in the following tables.
88
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021