Parameter
Output time for pulse operating
mode (setting only possible for
operating modes Pulse and
Pulse with retrigger)
Source Type Energy Counter
Energy counter
Energy increase per pulse
Output time for pulse operating
mode
15.3.1.3

SICAM Subdevices

Table 15-19
Parameter
Subdevice 1
Subdevice 2
Subdevice 1
Server IP address
Server port
Response timeout
Timeout [ms] ≤ (Communica-
tionSupervisionTime [ms] - 20
[ms]) / 2; CommunicationSu-
pervisionTime is a paramter of
the SICAM I/O Unit 7XV5673.
Parameter: Source of output 1-
N
Indication: Input 1-N
Parameter: Source of output 2-
N
Indication: Input 2-N
Parameter: Source of output 3-
N
Indication: Input 3-N
Parameter: Source of output 1-P
Indication: Input 1-P
Parameter: Source of output 2-P
Indication: Input 2-P
Parameter: Source of output 3-P
Indication: Input 3-P
Subdevice 2
Server IP address
64
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Default Setting
20 (* 10 ms)
-none-
62
1.00 Wh
20 * 10 ms = 200 ms
Settings for the SICAM Subdevices
Default Settings
-none-
No further indications are
displayed.
192.168.0.56
51 000
3 (* 10 ms)
64
Response-
Indication 3 from Remote
Binary inp. 1-N SICAM IO
1
Indication 4 from Remote
Binary inp. 2-N SICAM IO
1
Indication 5 from Remote
Binary inp. 3-N SICAM IO
1
Indication 6 from Remote
Binary inp. 1-P SICAM IO 1
Indication 7 from Remote
Binary inp. 2-P SICAM IO 1
Indication 8 from Remote
Binary inp. 3-P SICAM IO 1
192.168.0.57
Operational Indications and Operating Parameters
15.3 Advanced Functions
Setting Range
50 ms to 3 600 000 ms
Acc. to list box
0.10 Wh/VAh/varh to
1 000 000.00 Wh/VAh/varh
50 ms to 3 600 000 ms
Setting Range
-none-
SICAM IO
Any
(different from IP address of subdevice 2 and in
the same subnet as SICAM Q100)
10 000 to 65 535
10 ms to 60 000 ms
0 ms = invalid
Parameter:
Indication: any, max. 31 characters
Parameter Source of output:
Selection which indication is transmitted from
SICAM Q100 to the binary output of the SICAM
I/O Unit 7XV5673.
Indication Input:
Designation of the indication which shows the
status of the binary input of SICAM I/O Unit
7XV5673.
Any
(different from IP address of subdevice 1 and in
the same subnet as SICAM Q100)
357

Advertisement

Table of Contents
loading

Table of Contents