Commissioning and First Steps
11.5 Electrical Connection
NOTE
i
i
Always connect the grounding at the device to the terminal for the protective phase grounding (terminal
block H).
Terminals and Conductors
The device has the following terminal blocks:
Terminal Block
Terminals for supply voltage (H), inputs for current measurement (E), inputs for voltage measurement (F),
binary inputs (U), and binary outputs (G):
Conductor cross-section, rigid max.: 2.5 mm
Conductor cross-section (conductor with ferrule): 1.5 mm
Conductor cross-section (conductor with ferrule, terminal F): 2.5 mm
Tightening torque: 0.4 Nm to 0.5 Nm (3.5 in-lb to 4.5 in-lb)
RS485 interface (J) on the terminal side: RS485 cable with 9-pole D-sub socket
Ethernet interface (Z) on the top side: Ethernet patch cable or crossover cable
Functions of the Terminals
Terminal
E: I
A
L1
E: I
A
L1
E: I
B
L2
E: I
B
L2
E: I
C
L3
E: I
C
L3
E: I
N
E: I
N
F:
A
L1
F:
B
L2
F:
C
L3
F: N
G: 1
G: 2
G: 3
H (Earth)
H: N / -
H: N / +
284
E
4 inputs for alternating current measurement
F
4 inputs for alternating voltage measurement
H
Supply voltage
U
2 binary inputs
G
2 binary outputs
Assigned Function,
Measured Value or Indi-
cation
Ia
Ia
Ib
Ib
Ic
Ic
N
N
Van
Vbn
Vcn
N
Binary output 1
Root
Binary output 2
Protective phase
N/-
ph/+
Description
2
(AWG 14)
2
(AWG 16)
Description
Phase a, input, current measurement
Phase a, output, current measurement
Phase b, input, current measurement
Phase b, output, current measurement
Phase c, input, current measurement
Phase c, output, current measurement
Neutral phase, input current measurement
Neutral phase, output current measurement
Phase a, voltage measurement
Phase b, voltage measurement
Phase c, voltage measurement
Neutral phase, voltage measurement
Binary output 1
Common root for both binary outputs
Binary output 2
Neutral phase of the mains voltage or negative supply voltage
Phase of the mains voltage or positive supply voltage
2
(AWG 14)
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021