Technical Data; Power Supply; Inputs And Outputs - Siemens SICAM Q100 7KG95 Series Manual

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Technical Data

14.1 Technical Data
14.1
Technical Data

Power Supply

14.1.1
Direct Voltage
Rated input voltages
Admissible input voltage tolerance
Permitted ripple of the input voltage
Maximum inrush current
At ≤ 110 V
At 220 V to 300 V
Maximum power consumption
Alternating Voltage
Rated input voltages
System frequency at AC
Admissible input voltage tolerance
Permitted harmonics
Maximum inrush current
At ≤ 115 V
At 230 V
Maximum power consumption

Inputs and Outputs

14.1.2
Inputs for Alternating Voltage Measurements, Connector Block F - Cat III
Rated input alternating voltage range
Phase-N/PE
Phase-phase
Maximum input alternating voltage
Phase-N/PE
Phase-phase
330
24 V to 250 V
±20 %
15 %
< 15 A
≤ 22 A; after 250 μs: < 5 A
6 W
110 V to 230 V
50 Hz/60 Hz
±20 %
2 kHz
< 15 A
≤ 22 A; after 250 μs: < 5 A
16 VA
AC 57.73 V to 400 V (autorange)
IEC 61000-4-30 Class A:
Up to AC 230 V: 200 % overvoltage
> AC 230 V to 400 V: 200 % to 15 % overvoltage
UL conditions:
Up to AC 170 V: 200 % overvoltage
> AC 170 V to 300 V: 200 % to 15 % overvoltage
AC 100 V to 690 V (autorange)
IEC 61000-4-30 Class A:
Up to AC 400 V: 200 % overvoltage
> AC 400 V to 690 V: 200 % to 15 % overvoltage
UL conditions:
Up to AC 290 V: 200 % overvoltage
> AC 290 V to 520 V: 200 % to 15 % overvoltage
460 V (347 V for UL)
796 V (600 V for UL)
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021

Advertisement

Table of Contents
loading

Table of Contents