Operational Indications and Operating Parameters

15.1 Operational Indications

15.1
Operational Indications
Operational Indications
15.1.1
Indication
Description
Device OK
The device startup was successful.
Battery Failure
Battery voltage < 2.7 V or no
battery inserted
Time Synchronization
Error during the time synchroniza-
Error
tion from the NTP server or
fieldbus
Error during internal time synchro-
nization
Default IP Address
The device has started with a
default IP address after pressing
the F4 button for more than 3 s
during operation.
Primary NTP Server
Faulty or no response from the
Error
primary NTP server
Secondary NTP Server
Faulty or no response from the
Error
secondary NTP server
Daylight Saving Time
Switching between daylight saving
time/standard time
Ethernet Link Error
Ethernet connection error
Modbus TCP OK
At least 1 Modbus TCP server
connection has received Modbus
(Modbus TCP Server)
messages.
Modbus RTU Master
All configured Modbus slave
OK
devices respond to request tele-
grams.
342
Notes
Indication ON: Device ready
Indication ON: Battery failure
Indication OFF: At least 1 time message was received
during the set timer (Error indication after). The time
stamp is set when the first valid time information or time
synchronization is received.
Indication ON: No time message was received during the
set timer (Error indication after).
The time stamp is set after the Error indication after timer
has expired and no synchronization message was received.
Parameter range: see chapter
Error sources with NTP or fieldbus: Error indication after
timer expires and no synchronization message was received
Indication ON: RTC time invalid (during device start in case
of battery failure)
Indication OFF: After setting the clock via HTML
During battery failure at device startup
Indication ON: F4 was pressed and default IP is set in the
device.
Indication ON: Error
Indication OFF: Valid time messages have been received for
a configured period.
Only for time synchronization via Ethernet NTP
Indication ON: Error
Indication OFF: Valid time messages have been received for
a configured period.
Only for time synchronization via Ethernet NTP
Indication ON: Daylight saving time
Indication OFF: Standard time
Indication ON: Error
Indication OFF: Ethernet link recognized
Indication ON: At least 1 Modbus message was received
during the set communication supervision time. The time
stamp is set when the first valid message is received.
Indication OFF: No Modbus message was received during
the set communication supervision time
Indication ON: If all configured Modbus slave devices
respond successfully to request telegrams.
Indication OFF: If at least one Modbus slave device does not
respond to a request telegram or if at least one Modbus
slave device responds with a Modbus exception code.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021