Configuration via the User Interface

Configuration of the Modbus TCP to the Modbus RTU Gateway
The Modbus RTU Master protocol must have been selected under serial communication.
To change the settings of the Modbus TCP/Modbus RTU Gateway in the Configuration tab, proceed as
follows:
In the navigation window, click Communication Ethernet.
Select Modbus TCP for the Bus protocol.
[sc_Modbus-TCP-RTU-gateway_Q100, 3, en_US]
Figure 2-22
Configure the respective parameters according to the following table.
Table 2-10
Parameter
Activated
Unit ID of this device
54
Configuration Tab, Modbus TCP to Modbus RTU Gateway Settings
Settings for Modbus TCP/RTU Gateway
Default Settings
No
255
Setting Range
No
Yes
1 to 255
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021