Siemens SICAM Q100 7KG95 Series Manual page 213

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Parameter
Harmonic
voltages for the
template of EN
50160 HV
Mains signalling voltage
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Click Activation.
NOTE
i
i
The factory settings are based on EN 50160. If you have changed the settings, the set parameters are
applied after a device restart. It is possible to reset to the factory settings.
Value View of the EN 50160 Report
To display the EN 50160 report in the Value view tab, proceed as follows:
In the navigation window, click EN 50160 report.
[sc_q200_PQ_Report_evalu, 3, en_US]
Figure 7-30
Edit the text box directly or select the Start time and End time from the calendar.
Select a report from the Report list.
Click Generate report.
The report is displayed in a separate window and can be printed out or saved.
44
The frequency "YYY" and the limit "xxx" are based on the configured frequency.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Default Setting
Odd
H3: 3.0, H5: 5.0, H7: 4.0, H9: 1.3, H11:
harmonics
3.0, H13: 2.5, H15: 0.5, H17: u.c., H19:
u.c., H21: 0.5, H23: u.c., H25: u.c.
Even
H2: 1.9, H4: 1.0, H6: 0.5, H8: 0.5, H10:
harmonics
0.5, H12: 0.5, H14: 0.5, H16: 0.5, H18:
0.5, H20: 0.5, H22: 0.5, H24: 0.5
Supply voltage should be in -15.0 % to
+15.0 % deviation of the primary nominal
voltage.
99.0 % of "YYY" Hz MSV should be less
than "xxx" % of the primary nominal
44
voltage.
Value View Tab, EN 50160 Report
Power Quality
7.12 EN 50160 Report
Setting Options
213