Power Quality
7.12 EN 50160 Report
7.12
EN 50160 Report
Power Quality Reporting Functions
7.12.1
7.12.1.1
Function Description
The device generates an EN 50160 report (PQ report) automatically or manually. According to the standard
EN 50160, the device generates the report by analyzing the measurand including power frequency, supply
voltage magnitude, flicker, voltage unbalance, harmonics, and events (CBEMA/ITIC curve).
The EN 50160 report provides 2 templates and 1 user-defined mode:
•
EN 50160 LV&MV and EN 50160 HV
For the 2 templates, the limiting values are fixed, and the threshold values are referred to the standard
EN 50160:2007.
•
User-defined
In this mode, you can configure the limiting values.
When the events happen, the data is flagged in red in the measurement record. If the Flagging acc.
IEC 61000-4-30 is set as
7.12.1.2
Configuration and Value View via the User Interface
Configuration of the EN 50160 Report
To configure the settings of the EN 50160 report in the Configuration tab, proceed as follows:
•
In the navigation window, click EN 50160 report.
210
yes , the device hides flagged data in PQ report.