10.14 RAMP (Ramp Output)
(Note 8)
Can be specified only when the operation unit is a double-precision floating point real number (DF).
Outline of operation
● Scaling is carried out from the output default value, output target value, and output time (in
ms) specified by [S1], [S2], and [S3], and linear output is executed in accordance with the
time elapsed from the execution start.
Processing
Example 1) Operation unit: 16 bits (US, SS)
[i]...US,SS
[S1]...DT0:K1000
Execution condition
ON
OFF
5000
(target value)
1000
(default value)
0
Example 2) Operation unit: 32 bits (UL, SL)
[i]...UL,SL
[S1]...DT0:K5000
Execution condition
ON
OFF
5000
(default value)
1000
(target value)
0
Flag operations
Name
SR7
SR8
(ER)
10-58
[S2]...DT1:K5000
DT10 (Output value)
400
[S2]...DT1:K1000
DT10 (Output value)
400
Description
To be set in the case of out-of-range in indirect access (index modification).
To be set when the output time width specified by [S3] is out of the accessible range.
[S3]...DT2:K400
When the execution condition is switched on,
the data are initialized.
400 ms (time elapsed)
700
1100
Time (ms)
[S3]...DT2:K400
When the execution condition is switched on,
the data are initialized.
400 ms (time elapsed)
700
1100
Time (ms)
[D]...DT10
[D]...DT10