15.4 SEND (MEWTOCOL Master / MODBUS Master)
● As the communication cassette (Ethernet type) has an Ethernet-serial conversion function, the
internal interface operates with similar programs as the case of the CPU with built-in SCU. The
setting method and programming method are different from those for the CPU with built-in ET-
LAN. Refer to the section describing the case of SCU.
Flag operations
Name
SR7
SR8
(ER)
15-28
Description
To be set in the case of out-of-range in indirect access (index modification).
To be set when the source range is outside the accessible range.
COM port or connection specified by UNITSEL does not exist, or communication is not
possible in the specified connection.
Data device specified by [S] is invalid, or exceeds the area.
Sent data amount specified by [n] is invalid.
Station number specified by [D1] is out of the range.
Data device specified by [D2] is invalid, or exceeds the area.
Result storage device specified by [D3] is invalid.
Integer specification for [D2] is only available for the MODBUS direct address specification
type. It is invalid for other types.
Specified bit devices for [S] and [D2], and/or specified 16-bit device, differ.
WUME-FP7CPUPGR-12