X100
X101
DF
<Timing Chart 1>
X100
X101
Y110
Final timing with no
execution of the last
JP instruction
<Timing Chart 2>
X100
X101
Y110
Final timing with no
execution of the last
JP instruction
● If the same execution condition is used for the JP and differential instructions, rising (or
falling) of the execution condition for the differential instruction will not be detected. If the
differential output is necessary, be sure to write the differential instruction outside the range
between JP and LBL.
WUME-FP7CPUPGR-12
Since the execution condition X101 for the differential
instruction has not changed from t he final timing with no
execution of the last JP instruction, no differential output is
obtained.
Since the execution condition X101 for the differential
instruction has changed from OFF to ON from the final timing
with no execution of the last JP instruction, differential output is
obtained.
3.26 JP/LBL (Jump/Label)
JP 1
Y110
LBL 1
3-85