Time chart (in the case of CPU with built-in ET-LAN)
Master communication
clear to send flag
(X90 - X9F)
Master communication
sending flag
(Y90 - Y9F)
Execute RECV
Master communication
sent flag
(Y70 - Y7F)
Sending data
Response reception
processing
I/O allocation (in the case of CPU with built-in ET-LAN)
I/O number
Master communication
X90 to X9F
clear to send flag
Master communication
Y90 to Y9F
sending flag
Y70 to Y7F
Sent flag
(Note 1)
Each contact is used for reading the operation state. Do not write over it with a user program.
Precautions during programming (in the case of CPU with built-in ET-LAN)
● Use the UNITSEL instruction immediately before the SEND/RECV instruction to specify a
target connection number for communication.
● Master communication is only enabled when MEWTOCOL or MODBUS is selected. Confirm
that the "master communication clear to send flags" (X90 to X9F) are ON for the
corresponding connection, and execute the SEND/RECV instruction.
● The SEND or RECV instruction cannot be executed for the connection for which the master
communication is in progress. Confirm that the "master communication sending flags" (Y90
to Y9F) are OFF, and execute the instruction.
● The SEND or RECV instruction cannot be executed for the connection for which the slave
communication is in progress.
● Up to 16 SEND/RECV instructions can be executed simultaneously for differing connections.
● For communication between LAN ports of FP7, specify "U1" for the partner station number.
The receiver is determined by the IP address.
WUME-FP7CPUPGR-12
15.5 RECV (MEWTOCOL Master / MODBUS Master)
Check that the
flag is ON
Check that the
flag is OFF
Name
Turns ON when a connection is established in the master
communication.
Turns ON during sending data based on the SEND/RECV
instruction.
Turns OFF when the ED instruction is executed after the
completion of the response receive processing.
Reports completion result of sending data in genera-purpose
communication or master communication. (Normal completion: 0,
Abnormal completion: 1)
RECV instruction executable
conditions
Clear to send flag (X90 - X9F): ON
Sending flag (Y90 - Y9F): OFF
Sending flag (Y90 - Y9F):
While sending: ON
ED instruction executed following
response reception processing: OFF
Sent flag (Y70 - Y7F):
Normal completion: OFF
Abnormal completion: ON
Description
15-35