Panasonic FP7 Series Command Reference Manual page 954

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

17.12 FTPcSET (FTP Client Transfer Setting)
Setting
Settings
item
Conversion
method
(Note 1)
Input each source device setting parameter separated by a comma ",".
(Note 2)
Specify the operation setting parameters in the order of the above table.
(Note 3)
When omitting "Conversion method", it is set to unconverted 16-bit binary.
(Note 4)
The number of data that can be transferred simultaneously is 1MB for all 16 IDs. They are calculated
with file size.
Setting example
Exam
S3
"WX16,32,BIN1w"
ple 1
Device setting, Device division: Global, Device code: WX, Device number: 16, Number of
Settings
transferred data: 32 (32 words), Conversion method: Unconverted 16-bit binary
Exam
S3
"DT123456,250,SS"
ple 2
Device setting, Device division: Global, Device code: DT, Device number: 123456, Number of
Settings
transferred data: 250 (250 words), Conversion method: 16-bit signed decimal
Exam
S3
"WR0,16,DF"
ple 3
Device setting, Device division: Global, Device code: WR, Device number: 0, Number of
Settings
transferred data: 16 (64 words), Conversion method: 64-bit double-precision floating point
Exam
S3
"WL10,128"
ple 4
Device setting, Device division: Global, Device code: WL, Device number: 10 Number of
Settings
transferred data: 128 (128 words), Conversion method: Unconverted 16-bit binary
17-66
Specify a conversion method.
Parameter
BIN1w
Unconverted 16-bit binary
US
16-bit unsigned decimal
SS
16-bit signed decimal
UL
32-bit unsigned decimal
SL
32-bit signed decimal
32-bit single-precision
SF
floating point
64-bit double-precision
DF
floating point
HEX1w
16bitHEX
HEX2w
32bitHEX
HEX4w
64bitHEX
ASCII character (Output
ASCII
enclosed with "")
Extension (Saving
format)
.BIN (binary data)
.CSV
(comma-separated
text)
WUME-FP7CPUPGR-12
Setting
range