15.10 CONFIG (Change Configuration)
Flag operations
S1
MEWTOCOL
TCP-NODELAY
Precautions for programming
● Set this instruction to be executed only one time after switching to RUN.
● When specifying a device area for an operand, set string data using the SSET instruction in
advance. However, the ESSET instruction cannot be used because the format is different.
● Both upper and lower case letters can be used for operands.
● Not possible to execute while the built-in Ethernet is initialized. Before executing this
instruction, make sure that the IP address establishment flag (X62) is turned OFF.
Example of program (for enabling TCP-NODELAY option)
Flag operations
Name
SR7
SR8
(ER)
SR9
(Note 1)
Only when "MEWTOCOL" is specified for [S1].
(Note 2)
Only when "TCP-NODELAY" is specified for [S1].
15-66
S2
FL=DTx
FL=LDx
ENABLE
DISABLE
Description
To be set when the device specified by [S1] exceeds the area.
To be set when the device specified by [S2] exceeds the area.
To be set when a keyword that is not expected is specified.
To be set when the device corresponding to FL0 specified by [S2] exceeds the area.
Set when the number of characters for operand specifying character constant exceeds 256.
To be set for a device that does not have the Ethernet function.
Set when the instruction is the initialization of Ethernet.
The detail code set for SD29 is "11: Ethernet initialization active".
(Note 2)
Settings
Assign FL0 to the address DTx.
Assign FL0 to the address LDx.
The TCP-NODELAY option is enabled.
The TCP-NODELAY option is disabled.
(Note 1)
(Note 2)
WUME-FP7CPUPGR-12