Panasonic FP7 Series Command Reference Manual page 907

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

17.3 ETSTAT (Acquiring Ethernet Unit Information: FTP/HTTP/SMTP)
DT3
Transfer result
Latest transfer success
DT4-DT9
time
Latest transfer failure
DT10-DT15
time
Number of transfer
DT16-DT17
successes (Whole)
Number of transfer
DT18-DT19
failures (Whole)
DT20
LOG transfer setting
DT21-DT27
Status of LOG0
DT28-DT34
Status of LOG 1
DT35-DT41
Status of LOG 2
-
-
DT(21+7x)
Status of LOG x
-DT(27+7x)
Control relay
Each of the following bits is allocated for the control relay (1 word).
Bit no. 15
Transfer disable relay (bit 15)
0: Transfer enabled,
1: Transfer disabled
Transfer cancel request relay (bit 14)
0: Not cancel, 1: Cancel
Transfer direction relay (bit 5)
0: Send, 1: Receive
Execution result relay (bit 4)
0: Normal completion, 1: Abnormal completion
(Note 1)
The transfer direction relay (bit 5) is "0" for logging or an HTTP client.
(Note 2)
The transfer cancel request relay (bit 14) is "0" for logging or an HTTP client.
List of execution done codes
Code
Name
0
Normal end
Transfer server unset
1
error
Transfer setting unset
2
error
Destination group unset
3
error
4
Client registration error
WUME-FP7CPUPGR-12
Only the bit for each ID number that is set is turned ON.
The status data (7 words) for each of the 16 LOG numbers is read.
Control relay: 1 word
Execution done code: 1 word
Transfer done code: 1 word
Number of successful executions (individual): 2 words
Number of failed executions (individual): 2 words
8 7
4 3
0 0 0 0 0 0 0 0
0: Fixed
Description
To be set when the processing of a transfer request instruction is
completed successfully.
To be set when the setting of the server that is accessed during the
execution of a transfer request instruction is not completed.
To be set when the transfer setting for the transfer number that is specified
during the execution of a transfer request instruction is not completed.
To be set when the destination group setting for the transfer number that is
specified during the execution of a transfer request instruction is not
completed.
To be set when a process request to a client fails to register.
0
Transfer request relay (bit 0)
0: No request, 1: Request
Transfer active relay (bit 1)
0: Stop, 1: During transfer
Retry active relay (bit 2)
0: No retry, 1: During retry
Execution done relay (bit 3)
0: During process, 1: Instruction execution complete
17-19

Advertisement

Table of Contents
loading