Installation And Connection; Operating Environment; Installation Method - IMO VXSM75-1 Instruction Manual

Imo jaguar vxsm general purpose inverter
Table of Contents

Advertisement

2.
Installation and
Connection
2-1

Operating Environment

Install the inverter in an environment described
in Table 2-1-1.
Item
Specifications
Site
Indoors
Ambient
-10 to +50 degree C
temperature
Relative
5 to 95% (without condensation)
humidity
Atmosphere The inverter must not be exposed to
dust, direct sunlight, corrosive
gases, oil mist, vapor or water drops.
There must be little salt.
No condensation occurs due to
abrupt temperature changes.
Altitude
1,000 m max. (Refer to Table 2-1-2
for altitudes exceeding 1000 m.)
Atmospheric 86 to 106 kPa
pressure
Vibration
3mm
2 to 9 Hz
9.8m/s
9 to 20 Hz
2
2m/s
2
20 to 55 Hz
1m/s
2
55 to 200 Hz
Impact
<15g (IEC 61068-2-27)
Table 2-1-1 Operating environment
Altitude
Output current attenuation ratio
1000 m or less
1000-1500m
1500-2000m
2000-2500m
2500-3000m
Table 2-1-2 Output attenuation ratio in relation to altitude
2-2

Installation Method

(1) Securely mount the inverter in the upright
position on a rigid structure so that the
"VXSM" characters face front. Avoid
mounting the inverter upside down or avoid
mounting horizontally.
(2) Allow clearances for cooling air shown in
Fig. 2-2-1 to cool down the inverter which
generates heat during operation. The
generated heat is radiated upward. Do not
install the inverter below a heat sensitive
device.
2-1
10mm
Fig. 2-2-1
(3) The temperature of the heat sink rises to
(4) When installing the inverter inside a control
(5) When storing multiple inverters inside a
1.00
0.97
0.95
0.91
0.88
Above
100mm
Left
Right
VXSM
100mm
Below
about 90 degrees C during operation of the
inverter. Mount the inverter on a base made
of a material withstanding the temperature
rise.
WARNING
Install the inverter on a nonflammable
material such as metal.
Otherwise fire could occur.
panel or the like, take full consideration for
ventilation so that the ambient temperature
of the inverter does not exceed the
specification requirements. Do not install
the inverter in a poorly ventilated small
enclosure.
single unit or inside a control panel,
horizontal installation is recommended to
reduce mutual temperature effects. When
an vertical layout is adopted for an
unavoidable reason, install a partition plate
or the like between inverters to isolate the
heat of the lower inverter.
CAUTION
Do not allow lint, paper, wood chips,
dust, metallic chips or other foreign
matter in the inverter or do not allow them
attached to the heat sink.
Otherwise fire or an accident could occur.

Installation and Connection

10mm