Technical Data; Profinet Interface - AUMA ACE C 01.2 Profinet Series Manual

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Technical data

7.
Technical data
Information
7.1.

Profinet interface

Settings/programming the Profinet interface
The Profinet interface is set (assignment of device name as well as assignment of the IP address) using the Profinet engineering tools of
the DCS.
General data of the Profinet interface
Communication protocol
Network topology
Connection
Profinet connection
Transmission rate
Cable length
Device classes
Fieldbus access
Supported Profinet specification
Supported Profinet functions
Supported Profinet alarms
Supported network diagnostic and
management protocols
Profinet redundancy
Vendor ID
Ident Code
Profinet device type
Identification & Maintenance proper-
ties
Profinet Ident Nr.
DAP (Device Access Point)
42
The following tables include standard and optional features. For detailed information
on the customer-specific version, refer to the order-related data sheet. The technical
data sheet can be downloaded from the Internet in both German and English at ht-
tp://www.auma.com (please state the order number).
Profinet according to IEC 61158 and IEC 61784
Star topology, point-to-point wiring
Due to the switch function integrated within the AC 01.2, both line topology and redundant ring topology
(MRP) are available.
Ethernet IEEE 802.3
2-pair cabling in compliance with IEC 61784-5-3 Auto Polarity Exchange, Auto Negotiation and Auto
Crossover are supported.
2 x RJ-45
Connection via connector for field assembly, one RJ-45 connector for Cat.5 (K009.706) is included in
the scope of supply of the electrical connection.
100 Mbits/s (100BASE-TX), full duplex
Max. 100 m
I/O controller (usually the PLC/DCS)
I/O devices (field devices)
I/O supervisor (programming device, PC or HMI for diagnostics/commissioning)
Provider - consumer model
Version V2.32
Cyclic Profinet communication (RT)
Acyclic Profinet communication (Read/Write Record)
Status Alarm
Update Alarm
Port Data Change Notification Alarm
Sync Data Change Notification Alarm
ACD (Address Conflict Detection)
ARP (Address Resolution Protocol)
DCP (Discovery and Basic Configuration Protocol)
SNMP (Simple Network Management Protocol)
LLDP (Link Layer Discovery Protocol) in accordance with IEEE 802.1AB
These functions allow assignment of the Profinet device name, a graphic representation of the plant
topology, port-granular diagnostics as well as neighbourhood detection as the basis for quick commis-
sioning and easy device replacement.
Use of MRP (Media Redundancy Protocol) in compliance with IEC 62439 (switch function integrated
within AC 01.2)
319
1
AUMA-Actuator-AC01-2
I&M0 Profile ID:
I&M0 Profile Specification Type:
I&M0 Version:
I&M0 Supported:
0x013F; 0x0001
0x80010000
AC 01.2/ACExC 01.2 Profinet
62976
4
257
30
Actuator controls

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac 01.2 profinet

Table of Contents