AUMA ACE C 01.2 Profinet Series Manual page 39

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
Description of LEDs on connection board
Table 34:
MODS (Module Status)
Red LED: off +
Green LED: off
Green LED: illuminated
Green LED: 1 brief pulse
Red LED: illuminated +
LED NETS red: off
Red LED: illuminated +
Red NETS LED: illuminated
Green/Red LEDs:
Alternately blinking
Table 35:
NETS (network status)
Red LED: off +
Green LED: off
Green LED: illuminated
Green LED: 1 brief pulse
Green LED: blinking
Red LED: illuminated
Red LED: 1 brief pulse
Red LED: 2 brief pulses
Red LED: 3 brief pulses
Table 36:
LINK/ACT1, LINK/ACT2
(Link/activity port 1 / 2)
Red LED: off +
Green LED: off
Green LED: illuminated
Green LED: blinking
LED: Red
Description of LEDs on basis sub-assembly
Table 37:
LED
LED RESET: illuminated
DEBUG LED: illuminated
LED DEBUG: 1 brief pulse
DEBUG LED: briefly blinking (1
Hz)
DEBUG LED: slowly blinking (5
Hz)
CAN LED: illuminated
LED BA1 or LED BA2: are illu-
minated
DX LED: illuminated
Description of Profinet functional module
Status
Explanation
Not Initialised
No voltage or module in "SETUP" or "NW_INIT"
status
Normal operation
The module has aborted "NW_INIT" status
Diagnostic events
Diagnostic events available
Exception error
Device in "EXCEPTION" status
Fatal event
Internal device error
Firmware update
Do not cut power supply!
Status
Explanation
Offline
Absence of power supply or no connection to I/O
controller
RUN
Connection to I/O controller available
STOP
Connection to I/O controller available. However, I/O
controller is in STOP status or I/O data is incorrect.
Blink
Is used by engineering tools to identify the device
within the Profinet network
Fatal event
Internal error, combined with "MODS" LED.
Station name er-
Device name (station name) not yet set
ror
IP address error
IP address not yet set
Configuration er-
Identification incorrect
ror
Explanation
No Ethernet network connection and no data communication on port
1 or 2
Port 1 or 2 are correctly connected to the Ethernet network, however
without active data communication
Port 1 or 2 are correctly connected to the Ethernet network and data
communication is available
No function
Explanation
No Reset active, power supply available
Sub-assembly in Reset status
Sub-assembly in initialisation status
Debug mode active
Normal status (Profinet application active)
Error of internal CAN communication
Data communication active, network connection via port 1 or port 2
"Data Exchange" via Profinet