AUMA ACE C 01.2 Profinet Series Manual page 53

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
ID
Type
Parameters
PRM
5
U16
Start stepping OPEN
PRM
6
U16
End stepping OPEN
Table 57: Customer settings > Duty type monitoring
ID
Type
Parameters
Data length = 6 bytes
PRM
2121
enum
Duty type monitoring
PRM
2122
U16
Perm. run time
PRM
2123
U16
Permissible starts
Table 58: Customer settings > Motion detector
ID
Type
Parameters
Data length = 12 bytes
PRM
2554
enum
Motion detector
PRM
2555
MMSS01
Detect. time dt
Ac-
Default
Setting value
cess
R/W
0
Min = 0 [0.1 %]
Max = 999 [0.1 %]
R/W
1000
Min = 1 [0.1 %]
Max = 1000 [0.1 %]
Ac-
Default
Setting value
cess
R/W
0
0: Function not active
1: Function active
R/W
15
Min = 10 [min]
Max = 60 [min]
R/W
1200
Min = 1
Max = 1800
Ac-
Default
Setting value
cess
R/W
1
0: Function not active
1: Function active
R/W
50
Min = 10 [0.1 s]
Max = 1800 [0.1 s]
Appendix
Explanation
Setting the start of stepping
mode in direction OPEN
Setting the end of stepping
mode in direction OPEN
Explanation
Activate/deactivate duty type
monitoring
Excess of the permissible run
time within the last hour is mon-
itored. A warning is issued when
exceeding the permissible run-
ning time/h.
Excess of the permissible starts
within the last hour is monitored.
A warning is issued when ex-
ceeding the permissible starts.
Explanation
With active motion detection the
verification is made whether the
actuator position changes due
to the manual operation within
the detection time dt by the
travel difference dx. Con-
sequently, a mechanical move-
ment can be detected at output
drive (signal: 'Handwheel opera-
tion')
Setting the detection time dt
53