AUMA ACE C 01.2 Profinet Series Manual page 26

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Description of the data interface
Table 19: Byte 23: Failure
Bit
Designation
(process representation)
0
1
2
3
4
5
6
7
Fault
Table 20: Byte 24: Maintenance required
Bit
Designation
(process representation)
0
Mainten. mechanics
1
Mainten. seals
2
Mainten. lubricant
3
Mainten. contactors
4
Mainten. interval
5
6
7
26
Bytes 21 and 22: Input AIN 2
Byte 21 = high byte, byte 22 = low byte.
In Byte 9 und Byte 10 wird der Wert des zweiten, zusätzlichen freien analogen
Stromeingangs der Profinet Schnittstelle übertragen. Die Anfangs- und Endwerte
können an der AC über die Drucktaster und das Display eingestellt werden. (For
operation, please refer to the respective operation instructions for the actuator.)
If the measuring values are 0.3 mA below the initial value, a signal loss is indicated.
Der Wert wird in Promille (Wert: 0
Byte 23: Failure
Causes of the Failure signal in accordance with NAMUR recommendation NE 107.
Prm-Text-Def GSD file
Fault
Byte 24: Maintenance required
Causes of the Maintenance required signal in accordance with NAMUR
recommendation NE 107.
Prm-Text-Def GSD file
Maintenance mechanics
Maintenance seals
Maintenance lubricant
Maintenance contactors
Maintenance interval
Byte 25: Out of specification 1
Causes of the Out of specification signal in accordance with NAMUR recommendation
NE 107.
1000) übertragen.
Value
Description
No signal (reserved)
No signal (reserved)
No signal (reserved)
No signal (reserved)
No signal (reserved)
No signal (reserved)
No signal (reserved)
1
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
0
In bytes 15 and 16, no faults are active (all bits are set to
0).
Value
Description
1
Mechanic maintenance requirement (AUMA service)
0
No signal
1
Seal maintenance requirement (AUMA service)
0
No signal
1
Lubricant maintenance requirement (AUMA service)
0
No signal
1
Contactor maintenance requirement (AUMA service)
0
No signal
1
The set maintenance interval has expired.
0
No signal
No signal (reserved)
No signal (reserved)
No signal (reserved)
Actuator controls
AC 01.2/ACExC 01.2 Profinet